Fuel Requirements & Pipe Sizing - Generac Power Systems PowerPact 6561 Installation Notes

Air-cooled generator
Table of Contents

Advertisement

Gaseous Fuel Requirements and Installation
Page 16 thru 21 in the Installation Guidelines Air-cooled Generators
Most Generators using gaseous fuels have a higher kW rating on Propane vs Natural Gas.
Generac Guardian Series Air-Cooled (Evolution) generators require 3.5 to 7" of water column for
Natural Gas, and 10 - 12" Water column for Liquid Propane Vapor.
For NatGas, verify that the meter is capable of providing enough fuel flow to include all household
appliances and other loads.
Order New Gas Meter from the Utility if it needs to be upsized (Customer may have to place the
order)
LP Gas Requirements
With LP Gas, use only the vapor withdrawal system. This type of system uses the vapors formed
above the liquid fuel in the storage tank.
The minimum LP tank size is 250 gallons unless unit calculations dictate the use of a larger tank.
Vertical tanks which are measured in pounds will not usually meet the minimum requirements. A
1050LB vertical tank size is minimum required.
This section can be found in:
Page 7 thru 9 in the Generac Generator Sizing Guide
20