Specifications - IBC VX Series Installation & Operating Manual

Residential condensing boiler
Table of Contents

Advertisement

Specifications

Specification
CSA Input (Natural Gas or Propane) -
MBH
CSA Input (Natural Gas or Propane) -
kW
CSA Output - MBH
CSA Output - kW
AFUE (to be confirmed)
Minimum gas supply pressure (natural
gas or propane) - inch w.c.
Maximum gas supply pressure (natural
gas or propane) - inch w.c.
Ambient temperature:
Low °F / °C /
High °F / °C
Max. relative humidity (non-condensing)
Minimum water temp. °F / °C
Maximum water temp. (electronic hi-
limit) °F / °C
Max. ΔT - supply/return (electronic
fence) °F / °C
Max. water temperature lockout limit °F
/ °C
Power use (120Vac/60Hz) @ full fire -
Watts (without pumps)
Weight (empty) - lbs/Kg
Pressure vessel water content -
USG/Liters
Maximum boiler flow rate - USgpm
Minimum boiler flow rate - USgpm
Maximum operating water pressure* -
psig
Minimum water pressure - psig
Relief valve pressure (supplied) - psig
VX 110
VX 150
16.9-110
23-150
5-32.2
6.7-44
16.2-101.5
22-138.5
4.74-29.8
6.5-40.6
95%
95%
4
14
32°F / 0°C
32°F / 0°C
122°F / 50°C
122°F / 50°C
90%
90%
34 / 1
34 / 1
190 / 88
190 / 88
40 / 22.2
40 / 22.2
201 / 94
201 / 94
90
67 / 30.4
78 / 35.4
1.88 / 7.12
2.79 / 10.56
14
2
50
8
30
5
VX 199
30.6-199
8.8-58.3
29.2-183.7
8.6-53.8
95%
4
4
14
14
32°F / 0°C
122°F / 50°C
90%
34 / 1
190 / 88
40 / 22.2
201 / 94
79
90
88 / 39.9
3.51 / 13.29
19
25
3
4
50
50
8
8
30
30

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vx 110Vx 150Vx 199Ibgfsw1-0110Ibgfsw1-0150Ibgfsw1-0199

Table of Contents