Water quality
Warning
Water quality has a significant impact on the lifetime and performance of a boiler's heat
exchanger.
Improperly prepared water in a heating circuit may cause damage to the heat exchanger
through fouling or corrosion. Repeated or uncontrolled water fills will increase the potential for
damage.
High levels of dissolved solids or minerals may precipitate out of the fluid onto the hottest part
of the heat exchanger, impairing heat transfer and resulting in overheating and premature
failure. The amount of solids that may form on the heat exchanger will depend on the degree of
hardness and the total water volume in the system. A high water volume system with a low
hardness count may cause as much damage as a system with less volume and higher
hardness, so it is recommended to treat water so as to remove all dissolved solids. Other water
chemistry allowable limits are as follows:
Acidity pH is to be between 6.6 and 8.5
Chloride is to be less than 125 mg/l
Iron is to be less than 0.3 mg/l
Cu less than 0.1 mg/l
Conductivity is to be less than 400μS/cm (at 77°F [25°C])
7 grains/ gal (120 ppm)
Important: Ensure that these limits are acceptable for the other water-side components in the
system.
Shipped with the boiler:
1 x Wall mounting bracket
1 x Condensate trap assembly
1 x 30 psig pressure relief valve
1 x Outdoor temperature sensor
2 x ¼" x 2 ½" Lag screws/w flat washers
1 x Propane fuel conversion kit