8.3 Miscellaneous touchscreen controller errors

" Loop/Indoor Sensor"
"Insufficient Air Flow"
"Insufficient Water Pressure"
"Unknown Error"
Error - Max. Inlet/Outlet Sensor Temp. Exceeded. >
Check water flow Water temperature signal not
within acceptable range. Potential flow or sensor
failure. Consult service technician.
Blank – screen dark, but fan running Indicative of
power-surge damage to appliance
Controller is stuck in "service" mode after software
update.
Miscellaneous errors
Issue
91
8.3 Miscellaneous touchscreen controller errors
Diagnosis
The sensor
Check the P501 plug is
plug is not
fully engaged in the back of
engaged.
the controller board.
The sensor
Check the P501 plug is
plug is not
fully engaged in the back of
engaged.
the controller board.
Temperature
Test each temperature
sensor input
sensor for appropriate
problem.
readings and Replace
defective temperature
sensor.
Current outlet
Check water flow.
temperature
exceeds
operating limit.
Defective or
Check wiring to
disconnected
temperature sensor and
temperature
control module.
sensor.
Check temperature sensor.
Check transformer; replace
if damaged.
Check circuit board for
visible damage.
If update fails
Restarting returns the
or no updates
boiler to normal operation.
applied.