8.2.2 Hi Limit cut-off temperature error
Issue
Error – Water High-Limit
Exceeded
8.2.3 Low Water Cut-off error
Issue
Error - Low Water Cutoff
8.2.4 Aux. Interlock 1 or 2
Issue
Interlock 1 or 2 terminals are
open.
Hi Limit cutoff temperature Error
Diagnosis
Water temperature exceeds
hi-limit. Boiler is in hard
lockout mode.
Low Water Cutoff Error
Diagnosis
The Safety and Ignition
module has detected a low
water condition.
Aux. Interlock 1 or 2
Diagnosis
Jumper lead is loose or
compromised.
External safety is in an alarm
state.
90
Section: Troubleshooting
Fix
See
Resetting a boiler after a
hi-limit temperature lockout on
page
88.
Fix
See
Resetting a boiler after a
LWCO lockout on page
88.
Fix
Replace the jumper lead.
Inspect the external safety
devices.