Figure 24
Top view - minimum distance of exhaust vent to inside and outside corners
Warning
In areas of high snowfall, users must be advised to check side wall vent and air intake
terminations on a regular basis to ensure blockage does not occur.
Sidewall direct vent with stainless sidewall terminal must be terminated as follows:
The Stainless Sidewall Terminal (SST) 2 inch (IBC kit P-256 ) or 3 inch (IBC kit P-257 ) are
approved for use with this appliance.
Install the SST to comply with the minimum vent clearances listed in
Install the SST with the vent and intake pipes horizontally beside each other or vertically with
the vent pipe on top (see
vent cap must be installed with the openings directed up and down (see
side to side.
Figure 25
Allowed SST installation orientations
The SST vent/air connections fit Sched. 40 two inch or three inch PVC/CPVC pipe. PPs
pipe cannot be used with the SST. The pipes must extend completely through the wall as
shown below. The SST is an external fixture, and is not part of the sealed vent system that
runs inside the building.
Figure 25
). The vent pipe cannot be installed below the intake. The
33
3.7.6 Sidewall vent termination
Table 5
.
Figure 25
), and not