IBC VFC 15-150 Operating Instructions Manual

IBC VFC 15-150 Operating Instructions Manual

Natural gas conversion parts kit p-176
Hide thumbs Also See for VFC 15-150:

Advertisement

Quick Links

DANGER
Check the rating plate of the boiler
to ensure it is configured for the
fuel you are using.
Failure to perform the proper fuel
conversion when required can
result in an immediate hazard.
Operating any IBC boiler using a
fuel other than the fuel listed on
its rating plate is prohibited. If
these instructions are not followed
exactly, a dangerous situation can
result, leading to fire, explosion or
production of carbon monoxide,
which may cause property damage,
personal injury, or loss of life.
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer's
instructions and all applicable codes and requirements of the authority having jurisdiction. If the information
in these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide may result
causing property damage, personal injury or loss of life. The qualified service agency is responsible for the
proper installation of this kit. The installation is not proper and complete until the operation of the converted
appliance is checked as specified in the manufacturer's instructions supplied with the kit.
120-170 R2
VFC 15-150 / VFC 45-225
NATURAL GAS coNveRSioN PARTS KiT# P-176
NOTE
These instructions are to be closely followed, and referenced to the details in
the boiler's current certified Installation and Operating Instruction Manual.
The above listed modulating boilers are factory fire-tested to operate with natural
gas, or propane as ordered. The rating plate will be marked to indicate which fuel
the particular boiler has been set up with. Firing a boiler with a fuel other than what
is listed on the rating plate is prohibited unless the following conversion procedure
is completed by a qualified technician.
The boiler will automatically de-rate the maximum input at a rate of approximately
2% per 1,000' above 4,500'. The gas valves zero governor will ensure that the
gas:air mixture is not affected at altitude.
Important Note: If converting from Propane to Natural Gas - Order Propane
to Natural Gas Conversion Kit, IBC Part# P-174 from your authorized IBC
Distributor.
MODEl NuMbER
VFC 15-150
VFC 45-225
Table 1: Fuel Conversion Kits
WARNING
InCluded wITh ConVersIon KIT
(IBC ParT# P-176)
1 x rating Plate Fuel overlay - IBC Part# 80-114a
1 x Gas Valve Conversion label - IBC Part# 80-107B
1 x Installer Identifier label - IBC Part# 80-172a
1 x Instruction sheet - IBC Part# 120-170 r2
NATuRAl GAs
TO PROPANE
P-174
P-174
PROPANE TO
NATuRAl GAs
P-176
P-176
1

Advertisement

loading

Summary of Contents for IBC VFC 15-150

  • Page 1 Important Note: If converting from Propane to Natural Gas - Order Propane result, leading to fire, explosion or to Natural Gas Conversion Kit, IBC Part# P-174 from your authorized IBC production of carbon monoxide, Distributor.
  • Page 2 VFC 15-150 / VFC 45-225 NATURAL GAS coNveRSioN PARTS KiT# P-176 Refer to the details in the boiler’s current Installation and Operation Manual, DANGER section 3.3 - “COMMISSIONING”, 3.4 “FUEL CONVERSION” A combustion test must be done The low Fire (Zero-offset) valve and high Fire (Gas: air) ratio adjustment will have...
  • Page 3: Natural Gas

    VFC 15-150 / VFC 45-225 NATURAL GAS coNveRSioN PARTS KiT# P-176 clocking the Meter Turn off the boiler’s gas shut off valve. with a small (1/8” or 3 mm) flat screwdriver, open the inlet gas supply pressure test port by turning its center- (Natural Gas) screw 1 full turn counterclockwise.
  • Page 4 VFC 15-150 / VFC 45-225 NATURAL GAS coNveRSioN PARTS KiT# P-176 NOTE The Installer must fill in the information and affix the included fuel conversion labels to the boiler in the positions indicated after the conversion is completed 120-170 R2...

This manual is also suitable for:

Vfc 45-225