Dnp Data Formats; Device Profile Document - Ametek 90B Series Installation And Configuration Manual

Annunciator system
Table of Contents

Advertisement

A
PPENDIX
DNP D
F
ATA
ORMATS
The DNP Communication option is used to transmit point status (Binary Inputs)
to other devices. When the SER time-stamped alarms option is enabled, a
historical record of binary input change events and the time at which they
occurred can also be sent. The DNP Communications work in a slave mode and
operate over RS-232/485 or Ethernet. The DNP implementation is outlined in
the Device Profile Document.
D
P
EVICE
ROFILE
DNP V3.0

DEVICE PROFILE DOCUMENT

Vendor Name: AMETEK Power Instruments
Device Name: AN3200, using the Triangle MicroWorks, Inc. DNP3 Multi-Port Slave Source
Code Library
Highest DNP Level Supported:
For Requests:
For Responses:
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 00 and 01 (start-stop),
and 17 and 28 (index) are supported in addition to request qualifier code 06 (no range – or all
points). Static object requests received with qualifiers 00, 01 or 06, will be responded to with
qualifiers 00 or 01. Static object requests received with qualifiers 17 or 28 will be responded
to with qualifiers 17 or 28. For change-event object requests, qualifier codes 06 (no range)
and 07 and 08 (limited quantity) are supported. Qualifiers 17 or 28 are always returned.
Maximum Data Link Frame Size (octets):
Transmitted:
292
Received
292
Maximum Data Link Re-tries:
Configurable from 0 to 255
Requires Data Link Layer Confirmation:
Configurable as: Never, Only for multi-frame messages, or Always
Requires Application Layer Confirmation:
When sending multi-fragment responses (Slave devices only)
Sometimes
Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
C
D
OCUMENT
Level 2
Level 2
Device Function:
Slave
Maximum Application Fragment Size (octets):
Transmitted:
170
Received
50
Maximum Application Layer Re-tries:
None
i.
111