Series 90B Home Page; Web Pb Control - Ametek 90B Series Installation And Configuration Manual

Annunciator system
Table of Contents

Advertisement

SERIES 90B H
P
OME
AGE
Figure E-2 shows the home page with administrator logged in. The top bar of the home page displays
the current date/time (in UTC and local time), and latest alarm that is not acknowledged. The check
box – Enable 30 second auto-refresh, when checked, will refresh the top portion of the page (blue
box) every 30 seconds.
The web browser home page has a graphic display of the SERIES 90B that matches the system
configuration of the Annunciator. Figure E-2 below shows an SERIES 90B Annunciator system with 2
rows high by 4 columns wide and 4 different window sizes. The home page Annunciator graphic will
follow the A (Automatic Reset) or M (Manual Reset) operating sequence depending on which
sequence is selected on the Annunciator. (If the sequence on the Annunciator is not A or M, it will
default to M.) SERIES 90B inputs configured as critical or non-critical alarms (via the Annunciator
Configuration Software) can each have their own unique color to indicate alarm, normal or
acknowledged states. Figure E-2 below shows critical alarm input #3 in the alarm state. There are
Acknowledge and Reset pushbuttons provided on the home page for acknowledging the web page
windows. Inputs that have been disabled will have a user selectable color background to highlight
the disabled state.
Figure E-2. SERIES 90B Home page

WEB PB Control

The pushbuttons on the home page will be shown in the lower right cell if SERIES 90B option INTB is
selected. If options NPB or LPPB are selected, the pushbuttons will be shown underneath the
Annunciator. There is a selection box to allow the web pushbuttons to control the SERIES 90B
i.