Electrical; Certifications - Ametek 90B Series Installation And Configuration Manual

Annunciator system
Table of Contents

Advertisement

Electrical

Surge Withstand:
Electrical Fast Transient/Burst Immunity:
IEC 61000-4-4
Surge Immunity:
Dielectric Withstand:
1400 Vac or 2050 Vdc Inputs to Digital (test @ configuration port)
1400 Vac or 2050 Vdc Outputs to Digital (test @ configuration port)
1450 Vac or 2150 Vdc AC Integral Power Input to Digital (test @ configuration port)
350 Vac or 500 Vdc DC Integral Power Input to Digital (test @ configuration port)
1400 Vac or 2000 Vdc from Inputs to Outputs
1400 Vac or 2000 Vdc from Inputs to Power Input
250 V RMS from Input to Input when configured for Isolated Inputs
1400 Vac or 2000 Vdc from Outputs to Power Input
1200 Vac or 1700 Vdc from Output to Output
1400 Vac or 2000 Vdc from Inputs to Case
1200 Vac or 1700 Vdc from Outputs to Case
1400 Vac or 2000 Vdc from Integral AC Power to Case
350 Vac or 500 Vdc from Integral DC Power to Case
350 Vac or 500 Vdc from Communications Ports to DC Power
1450 Vac or 2150 Vdc from Communications Ports to AC Integral Power Input
Radiated RFI Immunity:
Conducted RFI Immunity: IEC 61000-4-6
Radiated Emissions:
Conducted Emissions:
Radiated Power Frequency:
Field
ESD Effects:

Certifications

CE:
Low Voltage Directive 73/23/EEC:
EMC Directive 89/336/EEC:
1
FM
Pending
UL
Pending
1
Requires FM option (refer to option codes). The required door may be supplied by Ametek, a
panel shop or the customer. The door must meet the FM standard for requiring a tool to open or
remove the door to allow access to the front of the Annunciator.
98
ANSI C37.90.1 (Oscillatory portion)
(2kV DC Power, 1kV I/O)
IEC 61000-4-5 (1kV Common Mode, line-to-ground)
IEC 61000-4-3 10 V/m
EN 61000-6-4 (EN55011)
EN 61000-6-4 (EN55011)
IEC 61000-4-8
IEC 61000-4-2
4kV contact 8kV air
3V
30 A/m
EN 61010-1:2001
EN 61326:1998
Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
Magnetic

Advertisement

Table of Contents
loading

This manual is also suitable for:

An-3200

Table of Contents