Indicators; Power Requirements - Ametek 90B Series Installation And Configuration Manual

Annunciator system
Table of Contents

Advertisement

Indicators

SYSTEM STATUS
This Green LED is on when the Common Service Module (CSM) is operating
properly
LED FAIL
This Red LED will light when a defective lamp is detected
REMOTE COMM
This Green LED will indicate the status of the communications ports
On steady: Both serial and ethernet port activity
Slow flash: Ethernet port activity, no serial port activity
Fast flash: Serial port activity, no ethernet port activity
Off: No activity on either the serial port or the Ethernet port
GROUND FAULT
This Red LED is on when the optional Ground Fault detector module detects a
fault.

Power Requirements

Input Power
19-29 VDC
38-58 VDC
100-250 VDC
88-132 VAC, 60 Hz
176-264 VAC, 50 Hz
Input Burden: Maximum 2.2 Watts/point (depends on window size and options
selected)
96
(Option F
24VDC)
(Option E
48VDC)
(Option C
125VDC)
(Option B
120VAC)
(Option A
230VAC)
Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL

Advertisement

Table of Contents
loading

This manual is also suitable for:

An-3200

Table of Contents