Repeat Relay Outputs

Repeat Relay Option RR
Individual relay per point
Follows field contact or alarm sequence, selectable in Software
Energized or de-energized Relay Coil, selectable in Software
Form A or Form B (N.O. or N.C.) Contact, selectable by Jumper
-Available with all window sizes
Repeat Relay Option 2RR
Two repeat relays per point
Follows field contact or alarm sequence, selectable in Software
Energized or de-energized Relay Coil, selectable in Software
Form A or Form B (N.O. or N.C.) Contact, selectable by Jumper
-Available with full or half size (option 2S) windows
Repeat Relay Option FRC
Individual repeat relay per point
Follows field contact or alarm sequence, selectable in Software
Energized or de-energized Relay Coil, selectable in Software
Form C (SPDT) Contact, selectable by Jumper
-Available with full or half size (option 2S) windows
Relay Operation
Follows Field Contact:
Follows Alarm Sequence: Repeat Relay Output Latches on Alarm until
Follows Alarm Display:
Relay operation selectable in Software per point
Relay Ratings:
24VDC @ 3.0 Amps
110VDC @ 0.1 Amps
120VAC @ 3.0 Amps
Resistive Load
92
Repeat Relay Output Follows Input Contact State
Acknowledged or Reset
Repeat Relay Output toggles on and off following
operation of window