Annunciator system
Table of Contents

Advertisement

Enable Internal Horn (Option HN)
When selected, this will activate the internal audible device upon any non-critical
or critical horn condition.
Internal Horn Silence (option AS)
The internal horn (option HN) may be automatically silenced after a fixed time.
To do this use the up and down arrows to the right of the value box to set the
required time. The maximum value is 240s and the resolution is 1.0s.
Note: A setting of 0 indicates that the auto-silence is not activated.
External Horn Silence (Option AS)
This will silence any external horn if selected for CSM Relay #1-4 in the time
increment selected. This will automatically silence the Critical, Non-Critical or
Ringback Horn when this option is included with the system. The maximum value
is 240s and the resolution is 1.0s.
Note: A setting of 0 indicates that the auto-silence is not activated.
Auto Reset
This will activate the Reset function continuously, eliminating the need to
manually press this. (Note: this only applies to alarm sequences that require the
reset function.)
Critical Audible has no affect on non-critical
This will make the operation of the non-critical horn independent of the critical
horn. See the previous section on the operation of the non-critical audible.
Critical Audible Pulsed
Non-critical Audible Pulsed
This will pulse the non-critical audible output upon an alarm.
Ringback Audible Pulsed
This will pulse the ringback audible output upon an alarm.
Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
This will pulse the critical audible output upon an alarm.
i.
77