Annunciator system
Table of Contents

Advertisement

Sequence
The alarm sequence for each input group is defined in this page. The Input
Configuration page was used to indicate which of the four available groups was
assigned to each input. This page identifies the sequence chosen for each
group.
Note: The four available groups can be set up for the same First-Out Sequence,
but each group is treated separately as its own first out group.
To change the alarm sequence, click on the entry then choose the sequence
from the list.
LN
Automatic reset, non-locking, no flash, no audible, no PB
AO
Automatic reset with lock-in of alarms, no flash
AONL
Automatic reset, non locking, no flash
AF
Automatic reset with lock-in of alarms
AFNL
Automatic reset, non locking
FR
Automatic reset with lock-in of alarms, flash reset
AM
Manual Reset with lock-in of alarms
FRM
Manual Reset with lock-in of alarms, flash reset
AS
First out fast flash, subsequent alarm steady, auto reset
ASFR
First out fast flash, subsequent alarm steady, auto reset, w/ silence
ASFRM
First out fast flash, subsequent alarm steady, first out reset, w/silence
TFS
First out, triple flash, first out reset
TFSFRM
First out, triple flash, first out reset, flash reset, reset
TFSM
First out, triple flash, first out reset, reset
ARR
Ringback, dual flash, lock-in of alarms until acknowledged
FRR
Ringback, dual flash, lock-in of alarms until acknowledged, flash reset
VS
First out, dual color, single flash, with first out reset
VSRR
First out with ringback, dual color, dual flash, with first out reset
MC
Motor Control