10. TECHNICAL SPECIFICATIONS
10.1.
TECHNICAL CHARACTERISTICS
Accuracy is indicated as [%reading + (no. of digits) * resolution] at 23°C ± 5°C, <80%RH
DC Voltage
Range [V]
3
1500
AC TRMS Voltage
Range [V]
3
1000
Frequency range: 42.5 ÷ 69Hz ; Voltages zeroed for measured value <3V
Insulation Resistance (M) R(+), R(-), Rp – DUAL mode
Test voltage DC [V]
250, 500, 1000, 1500
(*) Accuracy given for VPN≥240V, Rfault≥10
Rp and R(-) not declared if R(+) <0.2M
Open circuit voltage
Short-circuit current
Rated test current
Insulation resistance (M) – TIMER mode
Test voltage DC [V]
250, 500, 1000, 1500
Open circuit voltage
Short-circuit current
Rated test current
Selectable Timer:
Continuity of protective conductors (RPE)
Range []
0.00
9.99
10.0
99.9
100
1999
>200mA DC up to 5 (cables included), resolution 1mA, accuracy (5.0%reading + 5digits)
Test current:
Open-circuit voltage
4 < V
GFL – Ground Fault Locator
Test voltage DC [V]
250, 500, 1000, 1500
(*) Accuracy given for VPN≥240V, Rfault≥10
Rp and R(-) not declared if R(+) <0.2M
Open circuit voltage
Short-circuit current
Rated test current
The GFL function allows obtaining correct results ONLY at the following conditions:
Test carried out on a single string
Single fault of low insulation located at any position in the string
Insulation resistance of the single fault <0.1M
Due to the random nature of these faults, it is recommended to carry out the measurements in environmental conditions similar to
those in which the fault was reported
Range [M
0.1
1.0
20
. Accuracy of Rp and R(+) not declared if R(+)≥0.2M
and R(-) ≥0.2M
<1.25 x rated test voltage
<15mA (peak) for each test voltage
> 1mA on R = 1k x Vnom (with VPN, VPE, VNE= 0)
Range [M
0.01
10.0
<1.25 x rated test voltage
< 15mA (peak) for each test voltage
> 1mA on R = 1k x Vnom (with VPN, VPE, VNE= 0)
3s ÷ 999s
< 10V
0
Range [M]
Resolution [M]
0.1 0.99
1.0 19.9
20 100
. Accuracy of Rp and R(+) not declared if R(+)≥0.2M
and R(-) ≥0.2M
<1.25 x rated test voltage
<15mA (peak) for each test voltage
> 1mA on R = 1k x Vnom (with VPN, VPE, VNE= 0)
disconnected from the inverter, any dischargers and functional ground connections
Resolution [V]
1
Resolution [V]
1
]
Resolution [M
0.01
0.99
0.1
19.9
1
100
]
Resolution [M
0.01
9.99
0.1
99.9
Resolution []
0.01
0.1
1
0.01
0.1
1
EN - 34
Accuracy
(1.0
reading + 2digits)
Accuracy
(1.0
reading + 3digits)
Accuracy (*)
]
reading
(5.0
and R(-)<0.2M
Accuracy
]
(5.0
reading + 5digits)
Accuracy
(2.0
reading + 2digits)
Accuracy Rp(*)
(5.0rdg + 5dgt)
and R(-)<0.2M
PV-ISOTEST
+ 5digits)
, Accuracy of
Position
accuracy
1module