PV-ISOTEST TABLE OF CONTENTS PRECAUTIONS AND SAFETY MEASURES ............... 3 1.1. Preliminary instructions ..................... 3 1.2. During use ......................... 4 1.3. After use ..........................4 1.4. Definition of measurement (overvoltage) category ............4 GENERAL DESCRIPTION ................... 5 ...
PV-ISOTEST 1. PRECAUTIONS AND SAFETY MEASURES The instrument has been designed in compliance with directive IEC/EN61010-1 relevant to electronic measuring instruments. Before and while carrying out measurements, observe the following indications and read all notes preceded by the symbol with the utmost attention.
PV-ISOTEST 1.2. DURING USE Please carefully read the following recommendations and instructions: CAUTION Failure to comply with the caution notes and/or instructions may damage the instrument and/or its components, or be a source of danger for the operator. The symbol “...
PV-ISOTEST 2. GENERAL DESCRIPTION 2.1. FOREWORD This instrument has been designed to carry out safety tests on photovoltaic (PV) modules/strings in order to verify the parameters declared by the manufacturer. In addition, this instrument measures insulation/continuity on PV modules/strings/fields. 2.2.
PV-ISOTEST 3. PREPARATION FOR USE 3.1. INITIAL CHECKS Before shipping, the instrument has been checked from an electric as well as mechanical point of view. All possible precautions have been taken so that the instrument is delivered undamaged. However, we recommend checking it to detect any damage possibly suffered during transport.
When switching on the instrument, the initial screen appears for a few seconds. It shows: P V - I S O T E S T The instrument model (PV-ISOTEST) The manufacturer’s name The serial number (SN:) of the instrument S N : 2 0 3 4 5 6 7 8 ...
PV-ISOTEST 5. GENERAL MENU Pressing the ESC/MENU key in any condition of the MENU 14/09 -17:34 instrument displays the general menu screen, in which the : Voltage instrument may be set, the saved measures can be displayed : Insulation: and the desired measuring function can be selected.
PV-ISOTEST 5.1.3. General Move the cursor to General by using the arrow keys (,) 15/10 – 18:04 and confirm with ENTER. The instrument shows the screen AutoPowerOff : which allows activating/deactivating the the Auto Power Off Keys beep ...
PV-ISOTEST 6. OPERATING INSTRUCTIONS 6.1. RPE – CONTINUITY MEASUREMENT ON MODULES/STRINGS/PV FIELDS The purpose of this measurement is performing a continuity test of the protective and equipotential conductors (e.g.: from rod to earth and connected foreign earth) and earth rods of SPDs on PV installations. The test must be carried out using a test current >...
Page 13
PV-ISOTEST 4. Use the arrow keys or and select the position “><”. 15/10 – 18:04 The display shows the screen to the side. - - - I t e s t - - - - - - ...
PV-ISOTEST 6.1.2. Carrying out continuity measurements in Standard (STD) mode 1. Position the cursor onto RPE by using the arrow keys 15/10 – 18:04 (,) and confirm with ENTER. The display shows the - - - following screen. The symbol “STD” is shown on the display.
Page 15
PV-ISOTEST 6. Press the GO/STOP key to start the test. In case no error 15/10 – 18:04 conditions occur, the instrument displays the message - - - “Measuring…” as shown in the screen to the side. I t e s t - - - Measuring…...
PV-ISOTEST 6.1.3. Carrying out continuity measurements in Timer (TMR) mode 1. Position the cursor onto RPE by using the arrow keys 15/10 – 18:04 (,) and confirm with ENTER. The display shows the - - - following screen. 2. Use the arrow keys (,) to select the Timer mode. The...
Page 17
PV-ISOTEST 9. Press the GO/STOP key to start the test. In case no error 15/10 – 18:04 conditions occur, the instrument starts a series of 0 . 2 3 continuous measurements for the entire duration of the set Timer, emitting a short sound every 3s, and...
PV-ISOTEST 6.1.4. Anomalous situations 1. To zero the value of compensated resistance, carry out a 15/10 – 18:04 new compensation procedure with a resistance higher - - - than 5 as, for example, with open leads. The message “Zero Reset” appears on the display.
PV-ISOTEST 6.2. M – MEASUREMENT OF INSULATION ON PV MODULES/STRINGS/FIELDS The purpose of this function is measuring the insulation resistance of the active conductors of PV modules, strings and fields according to the prescriptions of IEC/EN62446-1 and IECEN61557-2 guidelines, with no need to use an external switch to short-circuit the positive and negative terminals.
Page 20
PV-ISOTEST 4. Use the arrow keys or and select the position “Lim.”. M 15/10 – 18:04 ( + ) ( - ) The display shows the screen to the side. V t e s t - - - - - - 5.
PV-ISOTEST 8. The instrument carries out the following measurements in M 15/10 – 18:04 ( + ) ( - ) a sequence: V t e s t 1 5 1 0 1 5 1 5 Insulation between positive pole (+) of the string and M ...
Page 22
PV-ISOTEST 6. Use the arrow keys or and select the position M 15/10 – 18:04 V t e s t ( - ) - - - “Time”. The display shows the screen to the side. M R i ( - ) - - - 7.
Page 23
PV-ISOTEST 10. If “Ri(-)≥Lim”, the instrument shows the message “OK”, M 15/10 – 18:04 V t e s t ( - ) 1 5 4 0 to indicate the positive result of measurement. M R i ( - ) >...
PV-ISOTEST 6.2.3. Anomalous situations 1. In case the instrument detects one of the following M 15/10 – 18:04 ( + ) ( - ) conditions: “|VPN| > 1500V”, “|VPE| > 1500V” or “|VNE| > V t e s t - - - - - - 1500V”, it stops the measurement, gives out a long...
Page 25
PV-ISOTEST 5. In case the instrument detects that the voltage between M 15/10 – 18:04 ( + ) ( - ) the positive and negative poles is greater than the test V t e s t 1 3 2 0 1 5 1 0 voltage set, the message "VPN>Vtest"...
PV-ISOTEST 6.3. GFL – SEARCHING FOR CONDITIONS OF LOW INSULATION ON PV STRINGS In GFL (Ground Fault Locator) function, the instrument is capable of providing an indication about the position of a possible single fault of low insulation located in a string of the installation due, for example, to infiltrations of water or humidity in the junction boxes of PV modules.
Page 27
PV-ISOTEST 6. Use the arrow keys or and select the position “Lim.”. 15/10 – 18:04 The display shows the screen to the side. M - - - 7. Use the arrow keys (,) to set the minimum limit threshold for insulation measurement, which can be selected between 0.05 M...
Page 28
PV-ISOTEST 10. With no fault conditions (Rp≥Lim), the instrument 15/10 – 18:04 shows the screen to the side and the message “OK” M > 1 0 0 appears on the display. V P N V P E V N E...
Page 29
PV-ISOTEST 14. In case a fault is present (Rp<Lim) in position NMOD 15/10 – 18:04 (between the second last and the last module), the M 0 . 0 instrument shows the screen to the side and the message “GND:Fault NMOD-1..NMOD” on the display.
PV-ISOTEST 6.4. DMM – MULTIMETER FUNCTION In this function, the instrument shows the RMS and DC values of voltages between the positive (+) and negative (-) pole, between the positive (+) pole and earth connection and between the negative (-) pole and earth connection, in order to check for the presence of AC components on input voltages.
PV-ISOTEST 7. STORING RESULTS The instrument allows saving max 999 measured values. The saved data can be recalled to the display and deleted at any moment, and, upon saving, they can be associated with up to a maximum of 3 levels of numeric markers relevant to the installation name, the PV string and the PV module (with max value 250).
PV-ISOTEST 7.2. RECALL OF DATA TO DISPLAY AND MEMORY DELETION 1. Position the cursor onto MEM by using the arrow keys MEM 15/10 – 18:04 D a t e T y p e (,) and confirm with ENTER. The screen to the side...
PV-ISOTEST 8. CONNECTING THE INSTRUMENT TO THE PC CAUTION The connection between instrument and PC is realized by means of cable C2006. In order to transfer the data onto a PC, it is necessary to install beforehand both the management software and the drivers of cable C2006 on the PC itself.
PV-ISOTEST 9. MAINTENANCE 9.1. GENERAL INFORMATION The instrument you purchased is a precision instrument. While using and storing the instrument, carefully observe the recommendations listed in this manual in order to prevent possible damage or danger during use. Do not use the instrument in environments with high humidity levels or high temperatures.
PV-ISOTEST 10. TECHNICAL SPECIFICATIONS 10.1. TECHNICAL CHARACTERISTICS Accuracy is indicated as [%reading + (no. of digits) * resolution] at 23°C ± 5°C, <80%RH DC Voltage Range [V] Resolution [V] Accuracy (1.0 1500 reading + 2digits) AC TRMS Voltage...
PV-ISOTEST 11. APPENDIX – THEORETICAL OUTLINE 11.1. MEASUREMENT OF POLARIZATION INDEX (PI) The purpose of this diagnostic test is to evaluate the influence of the polarization effects. Upon the application of a high voltage to insulation, the electric dipoles distributed in the insulation align in the direction of the applied electric field.
Page 38
PV-ISOTEST 12. ASSISTANCE 12.1. WARRANTY CONDITIONS This instrument is warranted against any material or manufacturing defect, in compliance with the general sales conditions. During the warranty period, defective parts may be replaced. However, the manufacturer reserves the right to repair or replace the product.