Altronix eFlow104NK8 and eFlow104NK8D convert a 120VAC 60Hz input into eight (8) fuse or PTC protected
12VDC or 24VDC outputs with a total of 10A max. Units include an unswitched aux. output. They also offers
a suite of features that includes fire alarm disconnect, over voltage protection, and low power disconnect which
prevents deep discharge of stand-by batteries. Dual input design allows power to be steered from two (2) factory
installed independent low voltage 12 or 24VDC Altronix power supplies to eight (8) independently controlled
fuse (eFlow104NK8) or PTC (eFlow104NK8D) protected outputs.
UL Listed Sub-Assembly for US Installations:
UL 294, 7th Edition** - UL Listed for Access Control System Units.
UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.
UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listed Sub-Assembly for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
ULC-S319-05 - Electronic Access Control Systems. Class I Equipment.
CSA C22.2 No.205 - Signal Equipment.
European Conformity
Battery
7AH
12AH
40AH
65AH
- 2 -
Overview:
Agency Listings:
Stand-by Specifications:
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
0.4A/10A
1A/10A
6A/10A
6A/10A
Fire Applications
24 hr. Stand-by/
5 min. Alarm
N/A
0.3A/10A
1.2A/10A
1.5A/10A
Access Control
Applications
Stand-by
5 Mins./10A
15 Mins./10A
Over 2 Hours/10A
Over 4 Hours/10A
eFlow104NK8(D)