For control circuit power supply
When the wiring for the control circuit power supply (L11/L21) is thinner than that for the main circuit power supply (L1/L2/L3),
install an overcurrent protection device (molded-case circuit breaker, fuse, etc.) to protect the branch circuit.
Servo amplifier
Molded-case circuit breaker
Frame, rated
current
MR-J5-10_
30 A frame 5 A
MR-J5-20_
MR-J5-40_
MR-J5-60_
MR-J5-70_
MR-J5-100_
MR-J5-200_
MR-J5-350_
MR-J5-500_
MR-J5-700_
MR-J5W2-22G_
MR-J5W2-44G_
MR-J5W2-77G_
MR-J5W2-1010G_
MR-J5W3-222G_
MR-J5W3-444G_
*1 To comply with the IEC/EN/UL/CSA standards, refer to the MR-J5 Safety Instructions and Precautions for AC Servos (IB(NA)-0300391)
for selection of molded-case circuit breakers and fuses.
Using servo amplifier with DC power supply input
When using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in this section.
■For main circuit power supply [G] [A]
Servo
Molded-case circuit breaker
amplifier
Frame, rated current
Power factor
improving
reactor is not
used
MR-J5-10_
30 A frame 5 A
MR-J5-20_
30 A frame 5 A
MR-J5-40_
30 A frame 10 A
MR-J5-60_
30 A frame 15 A
MR-J5-70_
30 A frame 15 A
MR-J5-100_
30 A frame 15 A
(3-phase power
supply input)
MR-J5-100_
30 A frame 15 A
(1-phase power
supply input)
MR-J5-200_
30 A frame 20 A
MR-J5-350_
30 A frame 30 A
MR-J5-500_
50 A frame 50 A
MR-J5-700_
100 A frame 75 A
*1 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
*2 Use the magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of
80 ms or less.
6 OPTIONS AND PERIPHERAL EQUIPMENT
202
6.10 Molded-case circuit breakers, fuses, magnetic contactors
*1
Fuse (Class T)
Voltage AC [V]
Current [A]
240
1
*1
Voltage AC
[V]
Power factor
improving
reactor is used
30 A frame 5 A
240
30 A frame 5 A
30 A frame 5 A
30 A frame 10 A
30 A frame 10 A
30 A frame 10 A
30 A frame 15 A
30 A frame 20 A
30 A frame 30 A
50 A frame 50 A
60 A frame 60 A
Fuse (Class K5)
Voltage AC [V]
Current [A]
300
1
Fuse
Class
Current [A]
T
10
15
20
30
40
60
80
Voltage AC [V]
250
Magnetic
*2
contactor
Voltage DC
[V]
400
DUD-N30
DUD-N60