Technical data
9.1
3RA6 compact starter
9.1.1
General technical data
General technical data
Article number
Device standard
Number of poles
Permissible ambient temperature
Storage
Shipping
Operation
Internal control cabinet temperature: up to + 40 °C
Internal control cabinet temperature: up to +60 °C
The permissible operating current of the compact starter reduces depending on the design version and the ambient
1)
temperature (ϑ
> 40 °C). You will find additional information in "General data (Page 25)".
V
Relative atmospheric humidity
Max. installation altitude
Adjustment range overload release and
rated operational current I
Rated frequency f
Maximum rated operational voltage U
Rated insulation voltage U
Rated impulse voltage U
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
According to IEC/EN 60721-3-1
According to IEC/EN 60721-3-2
According to IEC/EN 60721-3-3
0,1 ... 0.4 A
•
e
0,32 ... 1.25 A
•
1 ... 4 A
•
3 ... 12 A
•
8 ... 32 A
•
e
i
imp
3RA61.
3RA64.
3RA62.
3RA65.
IEC/EN 60947-6-2
3
°C
-55 to +80
°C
-55 to +80
°C
-20 to +60
1)
%
100
1)
%
80
1)
%
10 to 90
m
2000 m above sea level
without any restrictions
A
0,4
A
1,25
A
4
A
12
A
32
Hz
50 / 60
V
690
V
400
for 3RA6250-.E.3. and
3RA6500-.E.4. (Reversing
starter 32 A designs)
V
690
kV
6
9
245