3RA64/3RA65 compact starter with IO-Link
6.6 Functions
Actuator TRIPPED
The compact starter has shut down because a malfunction or short circuit has been
detected.
The actual trigger event can be identified by referring to the "RLT 0%" display window.
When the actuator is in the TRIPPED position, the 3RA64 compact starter (direct starter)
and the 3RA65 compact starter (reversing starter) can adopt the following statuses:
Table 6- 9
Actuator
TRIPPED
TRIPPED
Note
Turning the actuator manually to the TRIPPED position.
The actuator can also be moved to the TRIPPED position manually. In this case, it is not
possible to say whether a short circuit has occurred or whether the actuator has been moved
to the TRIPPED position manually simply by looking at the display elements. However, if the
actuator has been moved to the TRIPPED position manually, you can turn it back from the
TRIPPED position to the
circuit trip has occurred.
For additional information on eliminating malfunctions, please refer to "Shutdown on
malfunction (Page 61)".
For additional information on eliminating short circuits, please refer to "Short-circuit
protection function (Page 59)".
114
Actuator TRIPPED display elements (direct/reversing starter)
Mech. display
RLT 0%
No display
White display
READY position straight away. This will not be possible if a short
Compact starter status
Short circuit tripped
Malfunction (e.g. end of service life reached)
System Manual, 09/2014, NEB560060102000/RS-AA/006