3RA61/3RA62 compact starter
5.6 Commissioning
Current setting I
e
Set the operating current of the motor to be protected on the setting scale.
Figure 5-5
RESET M/A
Select manual or auto reset following an overload trip on the "RESET M/A"
(manual/automatic) selector switch:
● Manual reset: Following overload trip, set the 3RA61/3RA62 compact starter manually
using the blue reset button.
● Auto reset: Following an overload trip, the 3RA61/3RA62 compact starter is reset
automatically after 3 minutes. However, a manual reset can still be performed if you have
selected this setting.
Figure 5-6
For additional information on the manual and auto reset functions, please refer to "Overload
protection function (Page 57)".
84
Setting the current setting I
Setting RESET M/A on the compact starter
on the compact starter
e
System Manual, 09/2014, NEB560060102000/RS-AA/006
SIRIUS 3RA6 compact starter