As-I Mounting Module; General Technical Data - Siemens SIRIUS 3RA6 System Manual

Compact starter
Hide thumbs Also See for SIRIUS 3RA6:
Table of Contents

Advertisement

Technical data

9.3 AS-i mounting module

9.3
AS-i mounting module
9.3.1

General technical data

General technical data
Article number
Slave type
Suitable for AS-i master
to Spec.... (or higher)
AS-i slave profile IO.ID.ID2
ID1 code (factory setting)
Permissible ambient temperature
Operation
Storage/transport
Degree of protection
Operating voltage
AS-i
AUX PWR 24 V DC
Current consumption
AS-i
Total current of the external outputs
AUX PWR
3RA6970-3A, -3B, -3C, -3F
The maximum breakaway starting current/holding current is made up of the maximum breakaway starting current/holding
1)
current of the compact starter and of the electronics of the AS-i mounting module.
3RA6970-3D, -3E
2)
The maximum breakaway starting current/holding current is made up of the maximum breakaway starting current/holding
2)
current of the compact starter, the electronics of the AS-i mounting module, and the external outputs.
Max. length of the cables for the local
inputs for safe shutdown
Electromagnetic compactibility BURST according to IEC/EN 61000-4-4
Conducted interference
Electrostatic discharge
Field-based interference
258
According to IEC/EN 60721-3-1 (storage),
IEC/EN 60721-3-2 (shipping)
According to IEC/EN 60947-1
- max. breakaway starting current
1)
- max. holding current
- max. breakaway starting current
- max. holding current
According to EN 50295
According to IEC/EN 61000-4-2
According to IEC/EN 61000-4-3
3RA6970-3.
A/B slave
2.1 or higher
7.A.E
7
°C
-25 to +70
°C
-40 to +85
IP20
V
26,5 ... 31,6
V
24 V + 20%
mA
Max. 30
mA
Max. 500
mA
400
mA
200
mA
900
mA
700
m
Max. 30 m
kV
1/2
kV
6/8
V/m
10 (80 MHz to 2.7 GHz)
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006