Table 7- 24
3RA6970-3C
Compact starter status
Normal operation
AUX Power OFF,
undervoltage, overvoltage
Direction of rotation 1 switched on
Direction of rotation 2 switched on
Overload tripped
Short circuit tripped
Direction of rotation 1 and direction
of rotation 2 simultaneously
switched on
Checkback signal IN2
Checkback signal IN4
The AS-i mounting module is ready when
1)
- the AS-i mounting module is snapped onto a functionally ready compact starter and
- AS-i communication and AUX PWR are available.
The bit is only set if the output was already set before the undervoltage or overvoltage was detected.
2)
X: Bit set
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
7.12 AS-i mounting module for 3RA61/3RA62 compact starter
Inputs
D0
D1
AS-i
IN2
mounting
module
ready
1)
X
X
X
X
X
X
X
X
X
D2
D3
Group fault
IN4
X
X
X
X
X
Accessories
Outputs
D0
D1
Motor
Motor
"direction of
"direction of
rotation 1"
rotation 2"
X
X
2)
2)
X
X
X
X
225