Summary of Contents for Salda AMBERAIR COMPACT CXP

  • Page 1 AMBERAIR COMPACT CXP MOUNTING AND INSTALLATION INSTRUCTION...
  • Page 2: Table Of Contents

    8.7. WATER HEATER CIRCULATION PUMP AND VALVE ACTUATOR 8.8. PREHEATER AND COOLER 8.9. ELECTRICAL DIAGRAMS AND ABBREVIATION IN ELECTRICAL CIRCUIT DIAGRAMS 9. POSSIBLE FAULTS AND TROUBLESHOOTING 10. ECODESIGN DATA TABLE 11. DECLARATION OF CONFORMITY 12. WARRANTY 12.1. LIMITED WARRANTY COUPON | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 3: Symbols And Marking

    Figure 2.4. Technical label location and air duct indication (left side) side) Units tested and produced according to EC directives SALDA – associated member of the Eurovent association (Europe’s Industry Association for Indoor Climate (HVAC), Process Cooling, and Food Cold Chain Technologies) VDI 6022...
  • Page 4: Safety Instructions And Precautions

    Danger: Fumes Salda Antifrost system uses dis-balancing of an airflow and it may cause negative pressure in premises. Care must be taken when using the device in the premises together with another heating appliance that depends on the air in the premises. Such appliances include gas, oil, wood or coal-fired boilers and heaters, fireplaces, continuous flow or other water heaters, gas hobs, cookers or ovens that draw the air in from the room and the duct-exhaust gases out through chimney or extraction ducting.
  • Page 5: Information About The Product

    Control type: C1 MCB, C2 Pre-wiring. Not suitable for operation in pools, saunas and other similar premises. 4.2. DIMENSIONS AND WEIGHT Figure 4.2.1. AmberAir Compact 1 CX P R Figure 4.2.2. AmberAir Compact 1 CX P L AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 6 Figure 4.2.3. AmberAir Compact 2-4 CX P R Figure 4.2.4. AmberAir Compact 2-4 CX P L | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 7 AMBERAIR COMPACT E1-I30 E1-I50 E2-I30 W1-I30 W1-I50 W2-I30 W2-I50 W3-I50 Weight [kg] 2-CXP- 2-CXP- 2-CXP- 2-CXP- 2-CXP- 2-CXP-E2 2-CXP- 2-CXP- 2-CXP- 2-CXP- 2-CXP- AMBERAIR COMPACT E1-I30 E1-I50 E2-I30 W1-I30 W1-I50 W2-I30 W2-I50 W3-I50 Weight [kg] AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 8 AMBERAIR COMPACT E1-I30 E1-I50 E2-I30 W1-I30 W1-I50 W2-I30 W2-I50 W3-I50 Weight [kg] 4-CXP- 4-CXP- 4-CXP- 4-CXP- 4-CXP- 4-CXP-E2 4-CXP- 4-CXP- 4-CXP- 4-CXP- 4-CXP- AMBERAIR COMPACT E1-I30 E1-I50 E2-I30 W1-I30 W1-I50 W2-I30 W2-I50 W3-I50 Weight [kg] | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 9: Technical Data

    (class, dimensions LxWxH) According to EN 13141-7. Acoustic data: check the product page on www.salda.lt Control board with complete set of MCB controllers is integrated in all CX P units. List of possible fans and electrical heaters of the unit is present above. More details of the unit and each unit's component can be found on the "VentMaster"...
  • Page 10: Operating Conditions

    1 - Plate heat exchanger; 2 - Supply fan; 3 - Exhaust fan; 4 - By-pass damper; 5 - Heating coil (depends on the model); 6 - Control board; 7 - Extract air filters (panel); 8 - Supply air filter (panel). | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 11: Installation

    The product is heavy. Exercise caution when transporting and installing. AMBERAIR COMPACT [mm] [mm] [mm] 1 CX P 1707 1000 1900 2 CX P 2166 1200 2050 3 CX P 2398 1200 2164 4 CX P 2578 1200 2464 L1>L2 AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 12: Unpacking

    After unpacking AmberAir Compact 4 CX P, open the side covers and unscrew the supporting legs, which are used for trans- portation, from the fans. | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 13: Piping And Instrumentation Diagram

    By-pass damper actuator Outdoor air damper actuator Exhaust air damper actuator Fire alarm damper actuator I Fire alarm damper actuator II Supply air fan pressure sensor Exhaust air fan pressure sensor Outdoor air temperature sensor AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 14: Mounting

    • The installation of the base is shown on page 16. • AmberAir Compact 1 CX P is installed after alignment using a level. • AmberAir Compact 2-4 CX P is installed with its end raised by 0.5-1 α | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 15: Unit Placing And Mounting Positioning Requirements

    • When using the rails, the hinges should be unscrewed from the cover after screwing up its ends. The accessories bag contains screws for fas- tening the end of the cover that was previously held by the hinges. AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 16: The Installation Of The Supporting Legs For The Floor-Mounted Version

    • Otherwise, the drainage system must be insulated and must be provided with a heating cable and thermostat! 30 mm • The siphon (4) should not necessarily be downstream the recovery unit but below it. 50 mm 30 mm | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 17: Connection Of The Air Duct

    • When installing air ducts next to the ventilation equipment, brackets must be used. They suppress vibration and assure secure installation of the various system parts. The necessary brackets can be found in our catalogue or on our website https://select.salda.lt.
  • Page 18: Start-Up Recommendations

    • All electrical equipment protection elements are properly connected (if they are additionally used), • Cables and wires correspond to all applicable safety and functional requirements, diameters, etc., • Earthing and protection systems are properly installed, • Condition of all seals and sealing surfaces is correct. | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 19: Maintenance

    3. The removal of the doors of the floor-mounted version. To unscrew the covers, you can use the key attached as an accessory. AmberAir Compact 1 CX P has only two covers, while Compact 2-4 CX P has three. AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 20 • Unscrew the screws 1 and 2 of the side covers of AmberAir Compact 2-3 CXP. Carefully open the covers. Unscrew and carefully remove the middle cover No 3. The door must be screwed on after maintenance. Recommended tightening is 2,7 N-m. | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 21: Filters Maintenance

    Before starting any maintenance or repair works, make sure that the unit is disconnected from the electrical network and/or that the main circuit breaker is turned off. • Fan maintenance should be performed by experienced and trained staff only. • The fan should be inspected and cleaned at least once per year. AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 22: Heat Exchanger Maintenance

    • Then wash the cartridge with a weak hot water flow (excessively strong water flow may bend its plates). • The heat exchanger may be installed into the unit only when it is completely dry. • The heat exchangers are removed either from the top or from the bottom. | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 23: Electric, Water Heater Maintenance

    RESET button using a screwdriver or a similar object. • Heaters are equipped with 2 thermal protection devices: an automatic self-resetting protection device that is activated at +50 °C, and a manually restored protection device that is activated at +100 °C. AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 24: Control Board Maintenance

    • To reassemble, follow all maintenance steps in reverse order. When re-connecting cables, wires, hoses and connectors, make sure to match each wire, hose and connector to corresponding connection terminal and connector. | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 25: Control

    1. Selected control interface (remote control panel, MB-GATEWAY, etc.). The selected interface affects access to the information and settings, however, it does not affect the logic of control. Full access to the information and settings is available on ST-SA-Control, MB-GATEWAY WEB application and SALDA AIR mobile application. 2. Unit configuration (internal/external components, sensors and control board settings) For unit control instructions, refer to the operation manual of the existing control device.
  • Page 26: Connection Of Accessories

    Product AmberAir Compact CXP can be equipped with fire dampers for extract and supply air. Dampers are controlled by Spring-return actuators (A1/A2). Upon activation of DO1 and DO2 signals the dampers shall open. When DO1/DO2 is deactivated, the dampers shall close. Dampers can also be equipped with damper position switches.
  • Page 27: Connection Of Remote Control Panel Or Modbus

    8.5. CONNECTION OF SUPPLY AND EXHAUST AIR DAMPERS AmberAir Compact CXP units can be equipped with supply air and exhaust air dampers. Dampers are controlled by Open/Close or Spring-return actuators. M2, M3 - Open/Close or Spring-return damper actuators. Upon activation of DO5 the dampers shall open. Upon activation of DO6 the dampers with Open/Close actuators shall close.
  • Page 28: Preheater And Cooler

    PREHEATER AND COOLER AmberAir Compact CXP units can be equipped with external electrical or water preheater. Automatic and manual protection devices must be connected to MCB EX1 controller‘s X21 connector when electric preheater is equipped with these connection terminals. Otherwise, jumpers are installed in the X21 connector protection inputs.
  • Page 29 - N2 - N3 - N2 - N2 - N2 EX1 V1.0 EX1 V1.0 EX2 V1.0 EX1 V1.0 EX1 V1.0 EX1 V1.0 EX2 V1.0 0-10 VDC 24VDC -M16 -M14 Figure 8.9.3. External water cooler AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 30 - N2 - N2 EX1 V1.0 EX1 V1.0 EX2 V1.0 EX2 V1.0 Jumper* 0-10 VDC 24VDC Figure 8.9.4. External DX cooler Figure 8.9.5. Fire protection connection | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 31 Figure 8.9.6. Motorised air dampers EX1 V1.0 EX1 V1.0 -Transmitter2 Figure 8.9.7. CO or RH sensors AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 32 SP DI/DO UAB"SALDA" 2018-06-15 DRAWN BY All the external electrical connections must be implemented in accordance with effective legal acts and safety requirements. MCB I/O 2018-06-15 CHECKED BY Connections principal scheme 2018-06-15 APPROVED BY | EN AMBERAIR COMPACT CXP v2024.2...
  • Page 33: Possible Faults And Troubleshooting

    10. ECODESIGN DATA TABLE More details of the unit and each unit's component can be found on the "VentMaster" selection app. AMBERAIR COMPACT CXP v2024.2 EN |...
  • Page 34: Declaration Of Conformity

    Should any alterations be made in the products, this declaration will no longer apply. Notifi ed body: VšĮ Technikos priežiūros tarnyba, Naugarduko g. 41, LT – 03227 Vilnius, Lithuania, identifi cation number 1399. Quality: SALDA UAB activities are in line with the international quality management system standard ISO 9001:2015. Date...
  • Page 35: Warranty

    3.4. when the unit was used not for its original purpose. 3.5. Company SALDA UAB is not responsible for potential loss of property or personal injury in cases where the Air Handling unit is manufactured 3.5. Company SALDA UAB is not responsible for potential loss of property or personal injury in cases where the Air Handling unit is manufactured without the control system and the control system is installed by the client or the third parties.
  • Page 36 Look at the product label. ** - At least. NOTE. The customer shall be required to complete the Product Maintenance Table. MANUALS IN OTHER LANGUAGES https://select.salda.lt/file/ aacompactcxpde MAN000348 Ragainės g. 100 +370 41 540 415 Šiauliai LT-78109, LITHUANIA office@salda.lt...