Technical data

7
7 Technical data
140 | 150
Power supply (RDG200KN)
Operating voltage (L-N)
Frequency
Power consumption
No internal fuse!
External preliminary protection with max. C 10 A circuit breaker required in all
cases.
Before switching on power, select the right power supply needed using the
power switch on the rear of the device.
Outputs (RDG200KN)
Fan control Q1, Q2, Q3 – N
Qx rating min., max. resistive (inductive) 5 mA...5 (4) A
No internal fuse!
External preliminary protection with max. C 10 A circuit breaker required for all
cases.
Do not connect 3-speed fans in parallel!
Connect one fan directly, one relay for each speed for additional fans.
Use for actuator control (Q1, Q2)
Q1 - rating min., max.
resistive/inductive
Q2 - rating min., max.
resistive/inductive
Max total load current Q1+Q2+Q3
Use for external equipment (Q1, Q2,
Q3)
Rating min., max. resistive/inductive
Qx
Max total load current Q1+Q2+Q3
DC 0...10 V fan control; Y50-M
Control outputs
Y1, Y2, Y3, Y4-N
Yx power limitation
AC 24 V ±20 % or
AC 230 V +10/-15 % (selectable via
slider)
50/60 Hz
4 VA @ AC 24 V
7 VA @ AC 230 V
AC 24 V or AC 230 V (linked to power
supply)
5 mA...1 A
5 mA...1 A
5 A
5 mA...1 A
2 A
SELV DC 0...10 V, max. ±5 mA
Solid state (triacs)
AC 24 V or AC 230 V (linked to power
supply)
8 mA...1 A
3 A fast microfuse, cannot be
exchanged
A6V11545892_en--_a