Siemens RDG200KN Basic Documentation page 106

Room thermostats with knx communications
Hide thumbs Also See for RDG200KN:
Table of Contents

Advertisement

Functions
4
Communication objects (S-Mode)
Obj
Object name
75
Hum. Control
Inactive
mode
Humidification
Dehumidification
Indicates the mode of the humidity control function:
0 = inactive
1 = humidification; relative humidity lower than setpoint low P026
2 = dehumidification; relative humidity higher than setpoint high
P024
3...255 = not used
76
Enable electric
Enable/disable
heater
An electric heater can be disabled with this communication object
(e.g., to meet tariff regulations).
The same function is also available via local multifunctional input
X1/X2/U1 (P150, P153, P155).
Only one input source must be used, either local input X1/X2/U1or
KNX bus.
77
Built-in room
I/O
relative humidity
value [%r.h.]
The value of the room humidity measured via built-in sensor is
available on bus.
78
External room
I/O
relative humidity
value [%r.h.]
The thermostat receives and works with the relative humidity value
from an external sensor.
79
Room rel.
I
humidity: Setpoint
high
Communication object adjusts the humidity setpoint high used by
the thermostat. It changes the value of P024.
S-Mode object must be enabled by setting "Humidity setpoints" to
"as group object" in ETS.
The humidity maximum setpoint is stored in EEPROM. The
service life of the EEPROM depends on the number of write
cycles. Never write this communication object cyclically.
80
Room rel.
I
humidity: Setpoint
low
Communication object adjusts the humidity setpoint low used by
the thermostat. It changes the value of P026.
S-Mode object must be enabled by setting "Humidity setpoints" to
"as group object" in ETS.
The humidity minimum setpoint is stored in EEPROM. The service
life of the EEPROM depends on the number of write cycles. Never
write this communication object cyclically.
81
Reset the Energy
No action
efficiency status
Reset
(Green leaf)
Resets the settings to green leaf.
82
Energy efficiency
Green
status / Green Leaf
Red
Indicates current status of green leaf.
106 | 150
Function
Type/
Flags
length
20.115
CRT
1 byte
1.003
CWU
1bit
9.007
CRT
2 bytes
9.007
CWU
2 bytes
9.007
CWU
2 bytes
9.007
CWU
2 bytes
1.017
CWU
1 bit
1.006
CRT
1 bit
Obj
Object name
83
Enable or disable
Enable
Leaf indication
Disable
Enables or disables the leaf (green or red) indication.
84
Keypad: Lock fan
Lock
speed
Unlock
Locks or unlocks the fan operation keypad in current fan speed.
85
Keypad: Lock fan
Lock
speed in "auto"
Unlock
mode
Locks or unlocks the fan operation keypad in "auto" speed.
86
Keypad: Lock the
Lock
setpoint shift
Unlock
Locks or unlocks the setpoint shift keypad.
87
Keypad: Lock the
Lock
operating mode
Unlock
Locks or unlocks the operating mode keypad.
Function
Type/
Flags
length
1.003
CWU
1 bit
1.002
CWU
1 bit
1.002
CWU
1 bit
1.002
CWU
1 bit
1.002
CWU
1 bit
A6V11545892_en--_a