Technical data

Rated voltage
Overvoltage category
Frequency
Power consumption
No internal fuse!
External preliminary protection with max C 10 A circuit breaker required in all cases.
Fan control Q1, Q2, Q3-N
Rating
Fans must NOT be connected in parallel!
Connect one fan directly, for additional fans, one
relay for each speed.
Control output Y11-N / Y21-N (N.O.)
Rating
No internal fuse!
External preliminary protection with max C 10 A circuit breakers in the supply line
required in all cases.
Multifunctional input X1-M/X2-M
Temperature sensor input:
Type
Temperature range
Cable length
Digital input:
Operating action
Contact sensing
Parallel connection of several thermostats
for one switch
Insulation against mains voltage (SELV)
**)
Function of inputs:
External temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dew point monitor contact, enable
electrical heater contact, fault contact,
monitoring input
Interface type
Bus current
Modbus topology:
See Modbus manual (MODBUS over serial line specification and implementation
guide from
http://www.modbus.org
RDF302 Basic documentation
AC 230 V
III
50/60 Hz
Max. 7VA / 3.7 W
AC 230 V
5 mA...5(2) A
AC 230 V
5 mA...5(2) A
**)
NTC (3 k at 25 ° C)
0...49 ° C
Max. 80 m
Selectable (NO / NC)
SELV DC 0...5 V / max 5 mA
Max. 20 thermostats per switch
4 kV, reinforced insulation
Selectable
X1: P38
X2: P40
RS485 Modbus RTU,
Wire (ref.): 16 AWG, 1 pair,
shielded serial line with 1.5 mm
and length < 1200 m
Max. 50 mA
).
2
59 / 62
CE1P3079en
2022-06-17