Modulating control:
3-position, PWM or
DC 0...10 V
Note
Note
A6V11545892_en--_a
T[°C]
Room temperature
w
Room temperature setpoint
YHC1
Control command "Stage 1"
YHC2
Control command "Stage 2"
The diagrams below show the control sequence for modulating PI control.
Heating mode (P001 = 0)
Changeover (P001 = 2 or P001 = 3,
P254 = 0)
T[°C]
Room temperature
w
Room temperature setpoint
YHC1
Control command "Stage 1"
YHC2
Control command "Stage 2"
The diagrams only show the PI thermostat's proportional part.
For setting sequence and control outputs, see Application overview [➙ 37],
Sequence overview (setting via P001) [➙ 56] and Control outputs [➙ 78].
For applications with different signals, On/Off (1
heating/cooling P-band modulating (P050, P052), a small switching differential
SDH / SDC (P051, P053) is suggested to start 1
/ cooling demand is requested.
Set the heating flow limitation function with parameter P256 (RDG260KN)
when using a PICV in this application. See Additional functions [➙ 42].
Functions
Control sequences
SDH
Switching differential "Heating"
(P051)
SDC
Switching differential "Cooling"
(P053)
w
Setpoint differential (P056)
D
Cooling mode (P001 = 1)
Changeover (P001 = 2 or P001 = 3,
P254 = 1) (swap function)
XpH
Proportional band "Heating"
(P050)
XpC
Proportional band "Cooling"
(P052)
w
Setpoint differential (P056)
D
stage) and DC (2
st
sequence as soon as heating
st
4
stage),
nd