Technical Data - Siemens RDG100 Basic Documentation

Room thermostats with lcd for wall mounting
Hide thumbs Also See for RDG100:
Table of Contents

Advertisement

RDG100... / RDG110
Power supply
Outputs
Inputs
62 / 66
Siemens
Building Technologies
8

Technical data

Rated voltage
Frequency
Power consumption
RDG100 / RDG100T / RDG100T/H /
RDG110
Fan control Q1, Q2, Q3-N
Rating
Control outputs
Y1, Y2, Y3, Y4-N (RDG100)
Y11-N / /Y21-N (NO) (RDG110)
Multifunctional inputs
X1-M / X2-M
Temperature sensor input
Type
Temperature range
Cable length
Digital input
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
Insulation against mains
D1-GND
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
Insulation against mains
Function input
External temperature sensor, changeover sensor,
operating mode switchover contact, dewpoint
monitor contact, enable electrical heater contact,
fault contact
RDG100, RDG100T, RDG110, RDG140, RDG160
Technical data
AC 230 V
50/60 Hz
Max. 18 VA
2 W / 2 W / 1 W / 1.5 W
AC 230 V
Max. 5(4) A
AC 230 V, max. 1 A
AC 230 V, max. 5(3) A
QAH11.1 (NTC)
0...49 °C
Max. 80 m
Selectable (NO/NC)
DC 0...5 V, max. 5 mA
Max. 20 thermostats per
switch. Do not mix with D1!
N/A, mains potential
Selectable (NO/NC)
SELV DC 6...15 V, 3...6 mA
Max. 20 thermostats per
switch.
Do not mix with X1 / X2!
3.75 kV, reinforced
insulation
Selectable
Basic Documentation
CE1P3181en
14 Dec 2011

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdg110Rdg100tRdg160Rdg100t/hRdg140

Table of Contents