Example 3:
Swap and fan in the 2
nd
stage
A6V11545892_en--_a
2-pipe fan coil and 2-stage application with different types of equipment (On/Off
control outputs), the fan only operates if output V1 is energized.
Commissioning
●
Fan
●
Valve
●
Valve
See Technical data [➙ 140] for min. and
max. ratings
Outputs used
P350 = 5 (Heating
●
and 2
stage cooling)
nd
P201 = 2 (equipment
●
1)
P203 = 2 (equipment
●
2)
Connection
Application examples
M1
DC 0...10 V fan (2
stage)
V1
On/Off valve
(equipment 1)
V2
On/Off valve
(equipment 2)
RDG260KN
139 | 150
6