Connection
6
Application examples
Example 4:
Dehumidifier +
humidifier/DC 0...10 V fan
Example 5:
Dehum./3-speed fan
134 | 150
2-pipe fan coil application for dehumidification, with temperature setpoint shifting,
dehumidifier contact, DC 0...10 V fan and DC valve, humidification is controlled by
release contact:
Commissioning
Fan
Control strategy
Setpoint high
Setpoint low
Temp. shift
Valve
Relay function
Relay function
See Technical data [➙ 140] for min. and
max. ratings
2-pipe fan coil application for dehumidification, with temperature setpoint shifting,
dehumidifier contact (via external converter) and 3-speed fan:
Commissioning
Fan
Control strategy
Setpoint high
Temp. shift
Valve
See Technical data [➙ 140] for min. and
max. ratings
P351 = 3
(or DIP6 = OFF)
P450 = 1
P024 = 50 %
(factory setting)
P026 = 30 %
P461 = 3 K
(factory setting)
P201 = 5
P402 = 7 (Q3)
(dehum.)
P401 = 8 (Q2) (hum.)
P351 = 2
(or DIP6 = ON)
P450 = 1
P024 = 50 %
(factory setting)
P461 = 3 K
(factory setting)
P201 = 5
Outputs used
M1
DC 0...10 V fan
V1
DC valve
L2
Humidifier
*)
L3
Dehumidifier
*)
Release contact
*)
RDG260KN
Outputs used
M1
3-speed fan
V1
DC valve
C1
DC - On/Off
converter
L3
Dehumidifier
*)
Release contact
*)
RDG260KN