Siemens RDG200KN Basic Documentation page 83

Room thermostats with knx communications
Hide thumbs Also See for RDG200KN:
Table of Contents

Advertisement

RDG200KN
DIP NO.: 7...8 ➨ ON =
Y1/Y3 =
Y2/Y4 =
Notes
RDG260KN
Notes
A6V11545892_en--_a
The type of the control outputs (2- or 3-position) is set via DIP switches 7 and 8.
Patterns of DIP switches 7 and 8:
, OFF =
2-position (PWM)
2-position (PWM)
If 2-position (PWM) is selected via DIP switches, the control output is On/Off
(factory setting). To select PWM (pulse width modulation), set P201, P203
and/or P204 to 3.
4-pipe with electric heater: As the electric heater requires 1 of 4 outputs, only
the cooling valve actuator can be 3-position.
For commissioning via tool, all DIP switches have to be set to Off or related
application configuration. Control outputs need to be set via tools.
For details on connecting field devices and setting the DIP switches, refer to the
Mounting Instructions [➙ 5] [1] & [2]..
Applications with DC 0...10 V fan control (Y50) or without fan:
The type of valve actuator control outputs can be changed from DC 0...10 V
(factory setting) to On/Off.
To select On/Off valve actuator control, set P201 and/or P203 to 4 or DIP switch 7
and/or 8 to ON.
Example for 4-pipe application:
Cooling: DC 0...10 V Y10 (P201 = 5, default), On/Off on Q1 (P201 = 4)
Heating: DC 0...10 V Y20 (P203 = 5, default), On/Off on Q2 (P203 = 4)
When RDG260KN is set for chilled and heated ceiling with a 6-port ball valve, the
control output is Y10 and cannot be changed.
The fan type is selected via P351 or DIP switch 6, see Fan control [➙ 84]
RDG260KN On/Off valve actuator control on applications without fan function,
setting sequence:
Set DIP switch 6 to OFF and P351 to 3
Disable the fan function by setting P350 to 0
Set the valve actuators to On/Off by setting P201 and/or P203 to 4
For commissioning via tools, set all DIP switches to Off or the related
application configuration. The control outputs must be set using tools
Control outputs
2-position (PWM)
3-position
3-position
2-position (PWM)
Functions
4
3-position
3-position
83 | 150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdg260knS55770-t409S55770-t412

Table of Contents