Siemens RDG200KN Basic Documentation page 87

Room thermostats with knx communications
Hide thumbs Also See for RDG200KN:
Table of Contents

Advertisement

Note
2 sequences
heating/cooling
Fan in the 2
stage
nd
P350 = 4: 2
nd
P350 = 5: Heating and 2
cooling
P350 = 6: Cooling and 2
heating
P350 = 7: 2
nd
P350 = 8: 2
nd
Example 1
A6V11545892_en--_a
Fan speed III = Max. fan speed selectable via P359 (heating), P360 (cooling)
When heating with electric heater only, manual fan speed I is unavailable to
guarantee the necessary minimum air flow for the electric heater and to avoid
overheating.
For heating or cooling with 2 sequences (e.g. heating with a heating coil and an
electric heater, or 2-stage cooling), the fan is always synchronized to the 1
For 2-pipe and 2-stage applications, based on the equipment, the fan may have to
run in the 2-stage only (in the 1
cooling sequence.
The following settings are available by selecting fan control P350 accordingly:
stage
stage
nd
stage
nd
stage cooling only
stage heating only
The fan runs only in the 2
2-stage application).
Set both P201 and P203 to 4 or 5 (based on the requested control signal) and set
P350 to 4 (fan in the 2
Heating mode
stage the fan remains Off), either in the heating or
st
Fan runs in the 2
stage in heating and cooling (example 1
nd
or 2 when combined with the swap function)
Fan runs in heating mode and in the 2
(example 3)
Fan runs in cooling mode and in the 2
Fan runs in the 2
stage cooling only and not in heating
nd
mode
Fan runs in the 2
stage heating only and not in cooling
nd
mode
stage in the heating and cooling sequence (2-pipe and
nd
stage).
nd
Functions
4
Fan control
Note: Manual fan settings
do not influence control
signals "Heating" and
"Cooling".
stage.
st
stage cooling
nd
stage heating
nd
Cooling mode
87 | 150