6.3.2 Relay functions
Example 1:
Switching off the fan coil
unit
Example 2:
Switching on pumps
A6V11545892_en--_a
2-pipe fan coil application, fan coil unit off during Protection mode.
Commissioning
●
Fan
●
Valve
●
Relay function
See Technical data [➙ 140] for min. and
max. ratings
4-pipe fan coil application, pumps on during heating and cooling demand.
Commissioning
●
Fan
●
Valve
●
Relay function
●
Relay function
See Technical data [➙ 140] for min. and
max. ratings
P351 = 3
(or DIP6 = OFF)
P201 = 5
P402 = 1
(Protection mode)
P351 = 3
(or DIP6 = OFF)
P201/P203 = 5
P401 = 3
(heating pump)
P402 = 4
(cooling pump)
Connection
Application examples
Outputs used
●
M1
DC 0...10 V fan
●
V1
DC valve
●
L3
Fan coil
*)
●
K
Relay
Release contact
*)
RDG260KN
Outputs used
●
M1
DC 0...10 V
fan
●
V1, V2
DC valve
●
L2
Heating pump
*)
●
L3
Cooling pump
*)
●
K
Relay
Release contact
*)
RDG260KN
135 | 150