Siemens RDG200KN Basic Documentation page 133

Room thermostats with knx communications
Hide thumbs Also See for RDG200KN:
Table of Contents

Advertisement

Example 2:
Dehumidifier,
DC 0...10 V fan + valve,
No shifting setpoint
Example 3:
Dehum./DC 0...10 V fan,
On/Off valves
A6V11545892_en--_a
2-pipe fan coil application for dehumidification, with DC 0...10 V fan and DC valve
(without temperature setpoint shifting):
Commissioning
Fan
Control strategy
Setpoint high
Temp. shift
Valve
Relay function
See Technical data [➙ 140] for min. and
max. ratings
4-pipe fan coil application for dehumidification, with temperature setpoint shifting,
dehumidifier contact, DC 0...10 V fan and On/Off valves:
Commissioning
Fan
Control strategy
Setpoint high
Temp. shift
Valve
Relay function
See Technical data [➙ 140] for min. and
max. ratings
P351 = 3
(or DIP6 = OFF)
P450 = 1
P024 = 50 %
(factory setting)
P461 = 0
P201 = 5
P402 = 7
(dehumidifier)
P351 = 3
(or DIP6 = OFF)
P450 = 1
P024 = 50 %
(factory setting)
P461 = 3 K
(factory setting)
P201/P203 = 4
P402 = 7
(dehumidifier)
Connection
Application examples
Outputs used
M1
DC 0...10 V fan
V1
DC valve
L3
Dehumidifier
*)
Release contact
*)
RDG260KN
Outputs used
M1
DC 0...10 V fan
V1, V2
On/Off valves
L3
Dehumidifier
*)
Release contact
*)
RDG260KN
133 | 150