Functions
4
Room temperature setpoints
Setpoint priority
Setpoint master (RMB)
36 | 150
●
Local and central shifts are added up
●
Applies only to Comfort and Economy setpoints; Protection setpoints are not
shifted centrally
●
The current setpoint heating and cooling is limited by the Protection setpoint. If
the Protection setpoint is Off, both the minimum 5 °C and maximum 40 °C are
used
●
The current setpoints for cooling and heating of the same operating mode have
a minimum distance of 0.5 K
●
The result of local and central shifting, together with room operating mode,
humidity control or setpoint tracking for cooling, is used by the thermostat for
temperature control (current setpoint)
●
The room thermostat always takes over the setpoints received from the
controller RMB795B. Thus, the setpoints adjusted locally on the thermostats
are overridden by the setpoints from the room group (e.g., every 15 minutes)
–
On RMB, the circumstances under which the controller sends out the
setpoints can be defined. Refer to CE1P3122 for "Setpoint priority" and
"Setpoint Master" functions