6.11

Parameterize analog output AQ via the 3RW5 HMI High Feature

Operating principle
You can re-parameterize the output of the analog output with the 3RW5 HMI High Feature.
The actual average phase current L1 - L3 of the motor is displayed in % at the external
evaluation unit via the analog output. Depending on the respective connecting terminal being
used, the signal can be displayed either as current or voltage.
Requirements
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
6.11 Parameterize analog output AQ via the 3RW5 HMI High Feature
Terminals: AQ- / AQ I+
Measuring range of current output: 4 - 20 mA
Terminals: AQ- / AQ U+
Measuring range of voltage output: 0 - 10 V
3RW5 HMI High Feature (accessory)
Menu: "Parameters > Soft Starter > Analog output"
Access protection to 3RW5 HMI High Feature is not active or has been reset
Device version with analog output
Evaluation unit is connected properly (Page 232).
Parameter assignment