Installing The Standard 3Rw5 Hmi Into The Control Cabinet Door - Siemens SIRIUS 3RW52 Equipment Manual

Hide thumbs Also See for SIRIUS 3RW52:
Table of Contents

Advertisement

4.4.5

Installing the Standard 3RW5 HMI into the control cabinet door

Requirements
For using door mounting kit IP65:
Procedure without door mounting kit IP65
Place the 3RW5 HMI Standard in the cutout of the control cabinet door
3RW5 HMI Standard engages audibly in the 4 fixtures
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
3RW5 HMI Standard (accessory)
HMI connecting cable (accessory) of suitable length connected to the 3RW52 soft starter
Cutout of suitable size in the control cabinet door
Device depth of the Standard 3RW5 HMI:
– Total depth: 32 mm
– Embedded depth: 29 mm
Permissible wall thickness of the cabinet door:
– Without IP65 door mounting kit: 1.5 to 3.0 mm
– With IP65 door mounting kit: 1.0 to 7.0 mm
IP65 door mounting kit (accessory)
The fixing brackets with marking "001" are intended for a 3RW5 HMI Standard.
Screwdriver PZ2
4.4 Installing, mounting and removing the 3RW5 HMI
.
Mounting and dismantling