Siemens SIRIUS 3RW52 Equipment Manual page 122

Hide thumbs Also See for SIRIUS 3RW52:
Table of Contents

Advertisement

Parameter assignment
6.11 Parameterize analog output AQ via the 3RW5 HMI High Feature
Parameters
Parameter
Output signal type
Range start value
Range end value
Factor for calculating the output measured value
Measured value
Phase current average (%)
Example for calculating the parameters for the range start value and range end value
In this example, a pointer instrument indicates the measured value "Phase current average
(%)" at the left stop with 50% (start value) and the right stop 200% (end value). You can
divide the scale of the pointer instrument between the left stop and the right stop, depending
on the desired resolution.
The following parameters are given as examples at this point:
Output signal type: 4 ... 20 mA
Range start value = desired start value (%) / factor of the measured value
Range end value = desired end value (%) / factor of the measured value
Procedure
1. Parameterize the output signal type, e.g. 4 ... 20 mA.
2. Parameterize the range start value and the range end value taking the following factor
into account:
– Range start value (e.g. 50% / 3.125%)
– Range end value (e.g. 200% / 3.125%)
122
Description
Via the "Output signal type" parameter, you can define with what type of signal the
analog value will be output (current or voltage).
Deactivated
4 - 20 mA (factory setting)
0 ... 10 mA
With parameters "Range start value" and "Range end value", you can define which
value of the analog value to be output corresponds to the lower output signal value
and which to the upper output signal value. The respective value depends on the
coding of the measured value.
Factory setting:
Range start value: 0
Setting of the analog range, e.g. 4 mA = 0
Range end value: 96
Setting of the analog range, e.g. 20 mA = 96, corresponds to 300 % of the
average phase current (%).
Factor
3.125
Unit
Range of values
%
0 ... 796.9%
16
64
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
Coding
0 ... 255
SIRIUS 3RW52 Soft Starter