Table 5-4 Recommended Cable Sizes - Toshiba G9000 Series Installation And Operation Manual

480/480 v 300/500/650/750 kva
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

kVA
Input
Output
Capacity
Voltage
Voltage
300kVA
480V
480V
500kVA
480V
480V
650kVA
480V
480V
750kVA
480V
480V
*1 – The cables must be selected to be equal to the sizes listed in the table after accounting for site-specific conditions.
*2 – Voltage drop across power cables not to exceed 2% of nominal source voltage.
*3 – Allowable ampere-capacities based on 75C insulated copper conductor at ambient temperature of 40C.
*4 – All wiring to be in accordance with all applicable national and/or local electrical codes.
46
Table 5–4 Recommended Cable Sizes
Input Side
Cable
Torque
Size
ft. lbs.
29-39
(5) x 250 kcmil
(4) x 250 kcmil
ft. lbs.
29-39
(7) x 300 kcmil
(6) x 300 kcmil
ft. lbs.
29-39
(7) x 300 kcmil
(7) x 300 kcmil
ft. lbs.
29-39
(8) x 300 kcmil
(7) x 300 kcmil
ft. lbs.
G9000 Series UPS 300-750kVA Installation and Operation Manual – 61480-017
Output Side
Cable
Torque
Cable
Size
ft. lbs.
29-39
(4) x 250 kcmil
ft. lbs.
29-39
(6) x 300 kcmil
ft. lbs.
29-39
(7) x 300 kcmil
ft. lbs.
29-39
(7) x 300 kcmil
ft. lbs.
Bypass Side
Torque
Size
ft. lbs.
29-39
(8) x 250 kcmil
ft. lbs.
29-39
(10) x 300 kcmil
ft. lbs.
29-39
(12) x 300 kcmil
ft. lbs.
29-39
(15) x 300 kcmil
ft. lbs.
DC Input Side
Cable
Torque
Size
ft. lbs.
29-39
ft. lbs.
29-39
ft. lbs.
29-39
ft. lbs.
29-39
ft. lbs.