Daily Inspection; Table 9-1 How To Perform Daily Inspection - Toshiba G9000 Series Installation And Operation Manual

480/480 v 300/500/650/750 kva
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

9

DAILY INSPECTION

Please perform the daily inspection while the UPS is running. The daily inspection items are shown in Table 9.1.
!
NOTE
No. Subject
1.
Environmental
ambient
2.
Cabinet
Construction
3.
Operation
4.
LEDs
78
The customers can only inspect exterior or environment of cabinet. When the customers
want to perform the detailed inspection, contact the Authorized Toshiba Service
Representatives or call Toshiba International Corporation at 1-877-867-8773.
Table 9–1 How to Perform Daily Inspection
Procedure
Term
Period
Dust or Gas
Daily
Dewdrops
Daily
Condensation
Temperature
Daily
Humidity
Vibration or
Daily
Audible noise
Overheating
When needed Touching exterior
Air filter clog
When needed Visual check
LCD sharpness
Daily
Brightness
Left-bottom LED
Indication terms:
Daily
Output voltage
Output current
AC input voltage
Output frequency
Battery voltage
Battery current
DC voltage
4 status LEDs
Daily
2 fault LEDs
Daily
Criteria and/or Action needed
Method/Tool
Visual check and
Ventilate room atmosphere if dusty or smelling gas.
smelling
Visual check
Fix the dripping source
Dehumidify upon necessity.
Temperature: 32 – 104 F Humidity: 30 – 90%
Thermometer
hygrometer
No condensation.
To be controlled at about 77 F by A/C.
Touch and hearing
Check if fans have irregular sound.
Contact service representative in case of
abnormalities.
Contact service representative in case of
abnormalities.
Clean/wipe if clogged or dusty.
Visual check
No characters faded, illegible, or any other
abnormalities.
Left-bottom LED should be green.
Contact service representative when the LED
shows red with the backlight lost.
Visual check
Check indication terms/values if within the adequate
window.
Also check indication meters on surface of optional
cabinet, if installed.
Visual check
Check if LEDs turn on, off or flash according to the
operation.
Visual check
If UPS fault LED turns on, scroll the screen to see
fault codes and record the codes.
Contact service representative to tell about fault
codes and UPS symptom.
G9000 Series UPS Installation and Operation Manual – 61480-017

Hide quick links:

Advertisement

Table of Contents
loading