Advertisement

Installation Planning Guide for 750kVA UPS
Dimensions
(W x D x H)
Inches
90.6" x 32.8" x 80.7"*
* Height includes removable fan housing – Frame height is 78.7".
** 0" clearance for peripheral equipment, 1" clearance for walls.
Maximum Input Power Demand
Normal Mode (Recharge Mode)
kVA
PF
781 (840)
>0.99
Input Power Demand
kVA
PF
Amps
750
1.0
902
Battery Capacity Required
for Full Load Output
kWB
776 @ 1.0 PF
Rated Output Power
kVA
PF
Amps
750
1.0
902
Important Notes:
1.
Maximum input current is limited to 108% of the full-load input
current.
2.
Output load conductors are to be installed in separate conduit
from input conductors.
3.
Control wires and power wires are to be installed in separate
conduits.
4.
Recommended AC input and output overcurrent protection
based on continuous full load current per NEC 215.3.
5.
Wiring shall comply with all applicable national and local
electrical codes.
6.
Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
Primary AC Input: 3, 3-wire + ground.
-
Alternate AC Input: 3, 3-wire + ground.
-
AC Output: 3, 3-wire + ground.
-
-
DC Input: 2-wire (Positive/Negative) + ground.
7.
Nominal battery voltage based on the use of VRLA type batteries
(2.0 volts/cell nominal).
8.
Maximum battery discharge current based on lowest permissible
discharge voltage of 1.67 VPC.
86
Standard System: 480V Input, 480V Output
General Mechanical Information
Floor
Approximate Full-Load
Weight
Loading
Heat Rejection
2
Lbs.
Lbs./ft.
4255
207
Primary AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps (Max.)
939 (1010)
1300AT (1600AF)
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
1200AT
Battery Input (480VDC Nominal)
Maximum Discharge
Suggested External
at Full Load Output
Overcurrent Protection
Amps DC
1,940A
AC Output (480V 3-Phase / 3-Wire)
Suggested External Overcurrent
Protection
Amps
1200AT
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Btu/Hr.
Top
23.6"
79,147
Amps
250kcmil
9
External Feeder Wire Size Per Phase:
Cable Quantity of Below kcmil at 75º C Temp. Rating
250kcmil
300kcmil
8
7
Amps
250kcmil
2500AT
16
External Feeder Wire Size Per Phase:
Cable Quantity of Below kcmil at 75º C Temp. Rating
250kcmil
300kcmil
8
7
9.
DC wires should be sized to allow not more than a 2-volt drop at
maximum discharge current.
10. Weights do not include batteries or other auxiliary equipment external
to the UPS.
11. Cable sizing calculations based on the following method:
- Base cable ampacity is determined by 75
values in 2014 NEC Table 310.15(B)(16).
- Cable ampacity is derated for 40
Temperature per 2014 NEC Table 310.15(B)(2)(a).
- Cable ampacity is further derated for maximum possible of
conductors in Trade Size 4" EMT conduit per quantities shown in
2014 NEC Table C.1 and factors shown in Table 310.15(B)(3)(a).
- Cable meets bend radius limitations at the UPS terminals.
NOTE: Consult latest edition of applicable national and local
codes for possible variations.
12. Ratings of wires and overcurrent devices are suggested minimums.
Consult with a registered Professional Engineer within your local area
for proper size selections.
13. Overcurrent protection devices rated at 1200AT and above are
assumed to be rated for 100% continuous operation.
G9000 Series UPS Installation and Operation Manual – 61480-017
Front
Bottom
42.3"
0"
External Feeder Wire Size Per Phase:
Cable Quantity of Below kcmil at 75º C Temp. Rating
300kcmil
350kcmil
400kcmil
8
7
7
350kcmil
400kcmil
7
6
External Feeder Wire Size:
Cable Quantity of Below kcmil at 75º C Temp. Rating
300kcmil
350kcmil
400kcmil
15
14
13
350kcmil
400kcmil
7
6
o
o
C Ambient Operating
Sides**
Back
0"
0"
500kcmil
600kcmil
6
6
500kcmil
600kcmil
6
5
500kcmil
600kcmil
11
10
500kcmil
600kcmil
6
5
C rated copper conductor