Figure 5-15 Diagram Of Power Wire & Control Wire Connections For 3-4 Units In Mms Config. (300-750Kva) - Toshiba G9000 Series Installation And Operation Manual

480/480 v 300/500/650/750 kva
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

!
Use Ethernet STP (Shielded
Twisted Pair) Cable (Cat 5 or better)
with shielded RJ45 modular
connectors for all communication
cabling.
Use of UTP (Unshielded Twisted
Pair) Cable may cause malfunction.
TLAx and TLBx are redundant signal
lines. CAx and CBx are redundant
signal lines.
Redundant lines provide reduced
vulnerability to cable damage when
TLAx/CAx circuits are installed in
separate conduit from TLBx/CBx
circuits.
!
Total cable length from UPS-1
to UPS-N should be within 100m.
*1 Return from the last
UPS module to the first UPS
module (continuous loop).
*2 DIP switch position
UPS-1 and UPS-n: ON
Otherwise: OFF
*3 n = 3-4 (maximum) for this
cabling configuration
Figure 5-15 Diagram of Power Wire & Control Wire Connections for 3-4 units in MMS Config. (300-750kVA)
G9000 Series UPS Installation and Operation Manual – 61480-017
Communication
Cabling
*1
NOTE
NOTE
NOTE
UPS-1
IOAU-09
TN1
IFAU-09
CN99
5
TLBIN
6
CN98
TLAIN
*1
CN97
TLBOUT
CN96
TLAOUT
*2
ON
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
AC
OUTPUT
CN942
CA2OUT
A50
CN941
B50
CA1OUT
C50
*2
ON
UPS-2
IOAU-09
TN1
IFAU-09
CN99
5
TLBIN
6
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
*2
OFF
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
AC
OUTPUT
CN942
CA2OUT
A50
CN941
B50
CA1OUT
C50
*2
OFF
UPS-n
*3
IOAU-09
TN1
IFAU-09
CN99
5
TLBIN
6
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
*2
ON
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
AC
OUTPUT
CN942
CA2OUT
A50
CN941
B50
CA1OUT
C50
ON
*2
Toshiba Tie Cabinet (TTC)
Signal
Cabling
35
52L1-AX
36
37
52L2-AX
38
.
.
.
49
52Ln-AX
50
*3
Power
Cabling
AC OUTPUT
UPS-1
A
B
C
UPS-2
A
B
C
.
.
.
UPS-n
*3
A
B
C
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents