Figure 5-20 Automatic Startup Of Inverter And Converter; Figure 5-21 Close Battery Breaker; Figure 5-22 Press And Hold Start Button - Toshiba G9000 Series Installation And Operation Manual

480/480 v 300/500/650/750 kva
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

a.
f)
Close the Battery Breaker. (The START/STOP icon will not work until the battery breaker is closed.)
The display will show CB2 is closed and the battery backup is now online. (Figure 5-21)
g)
Press the STOP/START icon on the display, then press and hold the START button (Figure 5-22a) for two (2)
seconds until the UPS transfers to load on INV. (Figure 5-22b)
a.
66

Figure 5-20 Automatic Startup of Inverter and Converter

Figure 5-21 Close Battery Breaker

Figure 5-22 Press and Hold START Button

b.
b.
G9000 Series UPS Installation and Operation Manual – 61480-017