6 Mechanical Installation
NOTICE
Damage to Equipment. Remove the top protective cover from the drive when you install IP20/UL Type 1 models
2011 to 2169, 4005 to 4052, and 4077 to 4156 in an enclosure or when you install the drive with the heatsink external to the
enclosure. If you do not remove the cover, the drive temperature will increase and it can cause damage to the drive.
NOTICE
Damage to Equipment. Do not remove the top protective cover of model 4065. If you remove the cover, the drive
temperature will increase and it can cause damage to the drive.
Note:
When you install models 2011 to 2169 and 4005 to 4156 in an enclosure or when you install the drive with the heatsink external to the
enclosure, set L8-35 = 0 [Installation Method Selection = IP20/UL Open Type].
A - 50 mm (2 in) minimum
B - 30 mm (1.2 in) minimum
*1
For IP55/UL Type 12 enclosure drives, 50 mm (2 in) minimum is necessary to remove the front cover.
*2
This is the distance from a drive component or mounting bracket that has the maximum height. The highest component of the drive is
different for different models.

Side-by-Side Installation

Side-by-Side Installation lets you install more than one drive in the minimum mounting space. This method helps you
to use and set up a more compact control panel.
You can install drive models 2011 to 2114 and 4005 to 4124 side-by-side at ambient temperature 40 °C (104 °F).
Note:
You cannot install the drives that have IP55/UL Type 12 protection level side-by-side.
When you install IP20/UL Type 1 models 2011 to 2114 and 4005 to 4124 side-by-side:
• Use the clearances specified in
• Set L8-35 = 1 [Installation Method Selection = Side-by-Side Mounting].
• Set the derating for the ambient temperature.
NOTICE
Damage to Equipment. Remove the top protective covers from all drives when you install IP20/UL Type 1 models
2011 to 2114, 4005 to 4052, and 4077 to 4124 side-by-side. If you do not remove the covers, the drive temperature will increase and
it can cause damage to the drives.
NOTICE
Damage to Equipment. Do not remove the top protective cover of model 4065. If you remove the cover, the drive
temperature will increase and it can cause damage to the drive.
16
*1
Figure 6.2 Single Drive Installation Distances
Figure
6.3. Make sure that there is sufficient space.
C - 120 mm (4.7 in) minimum
D - Airflow direction
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation