Drive Parameters - YASKAWA HV600 Series Installation & Primary Operation

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600 Series:
Table of Contents

Advertisement

Type
Rotational Auto-Tuning
Stationary Line-Line Resistance
Type
Motor Parameter Setting
Line-to-Line Resistance

Drive Parameters

Icon
V/f
The parameter is available when operating the drive with V/f Control.
OLV/PM
OLV/PM
The parameter is available when operating the drive with Open Loop Vector Control for PM.
EZOLV
The parameter is available when operating the drive with EZ Open Loop Vector Control.
RUN
The parameter can be changed settings during run.
Note:
Gray icons identify parameters that are not available in the specified control method.
Refer to the following table when setting the most important parameters.
No.
(Hex.)
A1-00
Language Selection
(0100)
RUN
A1-02
Control Method Selection
(0102)
A1-03
Initialize Parameters
(0103)
b1-01
Frequency Reference Selection 1
(0180)
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation
Table 11.1 Auto-Tuning Mode Selection
T1-01
Recommended tuning mode for the most accurate results. Select this tuning mode when:
0
• You can decouple the motor from the load.
• You cannot decouple the motor from the load, but the motor load is less than 30%.
Select this tuning mode when:
• The drive and motor capacities are different.
2
• The drive is in V/f Control.
• You have replaced the drive and motor.
Table 11.2 EZ Tuning Mode Selection
T4-01
Set the motor parameters.
0
Select this tuning mode after you replace the drive, motor, and motor cables.
1
Name
V/f
OLV/PM
OLV/PM EZOLV
Sets the language for the HOA keypad.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
V/f
OLV/PM
OLV/PM EZOLV
Sets the control method for the drive application and the motor.
0 : V/f Control
5 : PM Open Loop Vector
8 : EZ Vector Control
V/f
OLV/PM EZOLV
OLV/PM
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
3410 : HVAC Initialization
V/f
OLV/PM EZOLV
OLV/PM
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Serial Communications
3 : Option PCB
11 Drive Control and Programming
Application Conditions and Benefits
Application Conditions and Benefits
Description
Description
A1-02 = 0
[Control Method
Selection = V/f]
Yes
Yes
A1-02 = 8
[EZOLV]
Yes
Yes
67