19 Troubleshooting
Code
Name
oPE03
Multi-Function Input Setting Err
oPE05
Run Cmd/Freq Ref Source Sel Err
oPE07
Analog Input Selection Error
oPE08
Parameter Selection Error
oPE09
PID Control Selection Fault
oPE10
V/f Data Setting Error
oPE11
Carrier Frequency Setting Error
oPE16
Energy Saving Constants Error
oPE33
Digital Output Selection Error
oPE34
HAND/OFF/AUTO Input Setting
oPE35
Network PI Aux Operation Mode
112
Causes
The settings for these parameters do not agree:
• H1-01 to H1-07 [Terminals S1 to S7 Function
Selection]
• H7-01 to H7-04 [Virtual Multi-Function Inputs 1
to 4]
The setting to assign the Run command or frequency
reference to an option card is incorrect.
The settings for H3-02 and H3-10 [MFAI Function
Selection] and H7-30 [Virtual Analog Input
Selection] overlap.
You set a function that is not compatible with the
control method set in A1-02 [Control Method
Selection].
These parameters are set at the same time:
• b5-01 = 1
• b5-11 = 1 [PID Output Reverse Selection =
Negative Output Accepted]
And one of these parameters is set:
• d2-02 ≠ 0.0 [Frequency Reference Lower Limit ≠
0.0%]
• Y1-06 ≠ 0.0 [Minimum Speed ≠ 0.0%]
• Y4-12 ≠ 0.0 [Thrust Frequency ≠ 0.0%]
• Y1-01 ≠ 0 [Multiplex Mode ≠ Drive Only]
• YF-01≠ 0 [PI Aux Control Selection ≠ Disabled]
The parameters that set the V/f pattern do not satisfy
these conditions:
• For motor 1: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤
E1-04 [Minimum Output Frequency ≤ Mid Point A
Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
• For motor 2: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤
E3-04 [Minimum Output Frequency ≤ Mid Point A
Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
These parameters are set at the same time:
• C6-05 > 6 [Carrier Freq Proportional Gain > 6]
• C6-04 > C6-03 [Carrier Frequency Lower Limit
> Carrier Frequency Upper Limit]
Note:
When C6-05 < 7, C6-04 becomes disabled. C6-
03 stays active.
The Energy Saving parameters are not set in the
applicable setting range.
These two parameters are set at the same time:
• H2-60 ≠ F [Term M1-M2 Secondary Function ≠
Not Used]
• H2-01 = 1xx [Term M1-M2 Function Selection =
Inverse output of xx]
When S5-04 = 0 [HAND-OFF-AUTO Behavior =
Legacy], H1-xx = 6D and 6E [MFDI Function
Selection = AUTO Command and HAND Command]
are set at the same time.
These parameter settings are not compatible:
• Y9-50 ≠ 0 [PI Auxiliary Control Source ≠ Analog
Only]
• Y9-51 = 1 [PI Aux Control Turn-Off Method =
Enabled]
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation
Possible Solutions
Correct the parameter settings.
Correct the parameter settings.
Set H3-02, H3-10, and H7-30 correctly to prevent overlap.
Note:
It is possible to set these functions to multiple analog input
terminals at the same time:
• Setting value 0 [Frequency Reference]
• Setting values F and 1F [Not Used]
1.
Push
to show U1-18 [oPE Fault Parameter], and find
parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other oPExx
errors have priority over oPE02.
Correct the parameter settings.
Set the parameters correctly to satisfy the conditions.
Set C6-02 to C6-05 correctly.
Make sure that E5-xx is set correctly as specified by the motor
nameplate data.
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
It is not possible to set H2-01 to H2-03 = 1xx [Inverse output of
xx] when using output functions for logic operations (H2-60,
H2-63, H2-66 ≠ F).
Set only one of the two functions H1-xx = 6D or 6E.
Examine the settings for Y9-50 and Y9-51.