Pressure Connection - YOKOGAWA Sushi Sensor XS530 User Manual

Pressure measurement module
Table of Contents

Advertisement

n Wireless Communication
Install where are no obstacles for radio waves such as walls or pipes around
the product as possible.
n Ambient Temperature
Avoid locations subject to wide temperature variations or a significant
temperature gradient. If the location is exposed to radiant heat from plant
equipment, provide adequate thermal insulation and/or ventilation.
n Ambient Atmospheric
Do not install the product in a location with a corrosive atmosphere. If this
cannot be avoided, ensure there is adequate ventilation.
n Shock and Vibration
It is designed to be resistant to shock and vibration. However, it is
recommended that XS530 be installed in a location that is subject to a
minimum amount of impact and vibration.
2.5

Pressure Connection

WARNING
Never loosen the process connection when an instrument is installed in a
process. The device is under pressure, and a loss of seal can result in a
sudden and uncontrolled release of process fluids.
The following precautions must be observed to safely operate XS530 under
pressure.
(a) Make sure that the process connection of XS530 is tightened firmly.
(b) Make sure that there are no leaks in the impulse piping.
(c) Never apply a pressure higher than the specified maximum working
pressure.
<Notes on Handling>
IM 01W06F01-01EN
2-3