2-8. ELECTRICAL
REQUIREMENTS
(Continued)
DRYWALL CONSTRUCTION
Secure I-bolt to a building
stud. Do not attach to drywall
only. Preferred installation is
approximately six inches to either
side of service. Cable restraint
must be at least six inches
shorter than flexible conduit.
Nov. 2007
An all pole, separate disconnect switch, with proper capacity
fuses or breakers must be installed at a convenient location
between the fryer and the power source, and must be installed
according to national and local codes. It should be an insulated
copper conductor rated for 600 volts and 90
than 50 feet (15.24 m), use the next larger wire size. CE units
require a minimum wire size of 6 mm to be wired to the terminal
block.
It is recommended that a 30 mA rated protective device such as
a residual current circuit breaker (RCCB), or ground fault circuit
interrupter (GFCI), be used on the fryer circuit.
Permanently connected electric fryers with casters must be
������������������������������
installed in the United States. See illustration at left. Holes are
available in the rear fryer frame for securing the cable restraint
to the fryer. The cable restraint does not prevent the fryer from
tipping.
The fryer is supplied with 2 different, 7 ft. (2.13 m) power
cord assemblies. The cord assembly with the NEMA L21-
20P�������������������������
Interlock Receptacle only, and supplies power to the controls.
The other power cord, supplying power to the heating system,
uses NEMA 15-60P Straight Plug, and each vat has its own power
cord assembly.
�������������������������������
cable, no lighter than ordinary polychloroprene or other
equivalent synthetic elastomer-sheathed cord.
2-5
Model LVE-102, 103, 104