Configuration; Usage - ABB RELION REB500 Operation Manual

Distributed busbar protection, version 8.3 iec
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Section 5
Local HMI
5.6.1

Configuration

The configuration of the LHMI Test Trip function includes the following two steps:
1.
Configuration of the tripping output signal:
Add (configure) the tripping signal 21120_EXT_TEST_TRIP HMI500 menu Configuration/
Binary module/Outputs to the bay specific binary output configuration see
Command
2.
Select the Enable the Test Trip check box from HMI menu Settings/Circuit-breakers/
Details window.
IEC19000206 V1 EN-US
Figure 65: LHMI Test Trip Configuration per Circuit Breaker
The current criteria can be enabled by selecting the Enable current criteria check box .
The current criteria value can be set to a value between 0.05 and 1.0 in steps of 0.05.
5.6.2

Usage

After configuring the LHMI Test Trip, the functionality can be used on a particular feeder's
LHMI. Use down and right arrow keys in the LHMI menu Test to find the Test Trip menu.
80
Section 4.6.3.6
Changed configuration settings take effect after downloaded to the
REB500 system (see
© Copyright 2019 ABB. All rights reserved
Section
4.4.1).
Distributed busbar protection REB500
1MRK 500 132-UEN B
GUID-B327D320-5E2E-43D1-9773-AC004578035B v1
Tripping
18000068-IEC19000206-1-en.vsdx
GUID-113837F4-2C01-4EF3-B96F-A635EBFBF5E1 v1